Справочник Пользователя для DCS 500

Скачать
Страница из 76
Chapter 4 - Signals and Troubleshooting 
 
 
 
 
 
DCS 500B / DCP 500B Operating Instructions 
IV A
  
4 - 1 
 
 
4.1 Display of status, alarm and fault signals 
 
Categories of signals 
and possibilities of 
display 
The signals (messages) to be available for thyristor power con-
verters series DCS 500B / DCF 500B or DCP 500 are subdivided 
into five  
categories: 
 General 
messages 
 
 Starting 
errors 
 
F
 Fault 
signals 
 
A
 Alarm 
signals 
 
[112 . .]
 
Status signals through parameters 
 
A seven segment display on the control board SDCS-CON-x of the 
thyristor power converters series DCS 500B / DCF 500B or 
DCP 500 is used to show general messages, starting errors, fault 
and alarm signals. The signals (messages) are displayed as codes. 
If the codes consist of several parts, the characters/individual digits 
will be indicated for 0.7 sec one after the other, e.g.: 
0.7s
0.7s
0.7s
 
F 14
 = Speed measurement fault 
 
 
 
 
 
In addition to this the DCS 500B DCF 500B or DCP 500 combined 
with the LCD of the control panel CDP 31x will be able to show the 
fault and alarm signals as well as the status signals (selected by 
signal numbers 
[112 . .]
) as clear text. 
Note:  
The languages to be available for display as text depend  
 
on the type of Control Panel and the Software version  
 ( 
 Chapter „Handling of Control Panel CDP 31x“). 
 
 
For subsequent evaluation via binary outputs or serial interfaces the 
16 bit informations 
FAULT WORD1
 
[11101], FAULT WORD2
 
[11102]
 
and
 FAULT WORD3 [11103]
 as well as 
ALARM WORD1
 
[11104], 
ALARM WORD2 [11105]
 and 
ALARM WORD3 [11106]
 contain several 
fault and alarm signals as a binary code. 
Each fault and alarm signal is coded as an individual error code to 
the 
LATEST FAULT [11106]
 and 
LATEST ALARM [11107
]
 
 
3ADW000055R0401_DCS500B_Operating Instruction_e_d