♦  Mount the connection cover of the cable clamping unit. 
5.2.2 
Connection Cross-Sections and Fuse Protection 
The required dimensions can be found in the following table: 
 PROTECT 
1.100
 
PROTECT 
1.150
 
PROTECT 
1.200
 
Max. current consumption 
(bypass)
 
46A 68A 91A 
Incoming mains cable 
(UPS input)
 
min. 
max. 
10 mm² 
16 mm² 
16 mm² 
35 mm² 
25 mm² 
35 mm² 
Load connection 
(UPS output)
 
min. 
max. 
10 mm² 
16 mm² 
16 mm² 
35 mm² 
25 mm² 
35 mm² 
Battery connection
 
Via 
enclosed 
battery 
connection 
cable 
protected 
against 
polarity 
reversal
 
Min. 16 mm², Max. 35 mm² 
per terminal 
Battery connection cable is 
included with the battery unit 
Observe earth-fault- and 
short-circuit-proof routing!
 
Mains fuse (UPS input)
 
50A gl 
80A gl 
100A gl 
 
When using line safety switches, observe 
trigger characteristic: “D”
 
Line safety switch “B” characteristic          
 
Load fuse 
(recommended max.)
 
16A          
20A    
25A 
* To ensure a reliable strain relief, individual wires must be laid 
especially for connecting the 15 and 20 kVA UPS systems. 
Recommended connection cable acc. to VDE 0298-4: 
 
Specially for 15 and 20 kVA:  
 
Special rubber-insulated wire 
NSGAÖU or NSGAFÖU 
or NYY or 
Radox 4GKW-AX 
e.g. Huber & Suhner 
Alternatively, the 10 kVA UPS system can also be connected 
via a multi-wire rubber-sheathed cable.