Справочник Пользователя для AEG Protect 1.150

Скачать
Страница из 64
 
 
46 
 Interfaces and Communication 
7.1 Computer 
Interface 
RS232 
For the control of the UPS and convenient reading of status 
messages and measured values, various interfaces are 
available. The interface protocol is designed for operation with 
the "CompuWatch" shutdown and UPS management software 
from AEG. Use the supplied RS232 communication cable to 
connect your PC. Plug the cable into a corresponding serial port 
on your PC. 
RS232 interface: The RS232 is connected via the 9-pin Sub-D 
socket strip on the back of the unit (no. 8, p. 27/28). Pin 
assignment: 2 = TxD; 3 = RxD; 5 = GND. 
7.2 Communication 
Slot 
On the back of the UPS, there is a cover (see p. 27/2828, no. 
7). When this is removed, additional, optionally available 
communication components can be installed there, e.g.: 
AS/400 board:
 Slot board with status messages, realised via 
potential-free relay contacts 
USB board:
 Slot board for communication via USB 
SNMP board:
 Slot board for direct connection of the UPS to 
the Ethernet network with RJ 45 (TCP/IP) 
Details can be found in the description enclosed with the 
particular optional component. Other boards in preparation. 
i
 
Using the communication slot deactivates the
RS232 interface from chapter 7.1. 
7.3 
Shutdown and UPS Management Software 
The "CompuWatch" software specially developed for these 
purposes by AEG continuously checks the mains supply and 
the UPS status. 
In conjunction with the “intelligent” UPS, this guarantees the 
availability of the EDP components as well as the data security.