10 
  Maintenance 
The PROTECT 1. consists of state-of-the-art, non-wearing 
components. We do, however, recommend visual checks 
(above all battery and fan checks) at regular intervals (at least 
every 6 months) to maintain continuous availability and 
operational reliability. 
 
CAUTION!
  
Ensure that the work area is cordoned off and 
always observe the safety instructions! 
 
10.1 
Charging the Battery 
The battery is automatically charged when the mains is 
connected, irrespective of the operating mode. This is signalled 
by the Load LED’s lighting up (see also chapter 4.4.2). 
The complete charging time of the battery after a long 
discharge time depends especially on the number of additional 
external battery units (see chapter 2.3). 
10.2 Checks 
The following maintenance work should be performed: 
Task Interval 
Described 
in 
Visual check 
6 months 
Chapter 10.2.1 
Battery/fan check 
6 months 
Chapter 0 / 0 
10.2.1 Visual 
Check 
When visually inspecting the unit, check whether … 
♦  there is any mechanical damage or foreign bodies can be 
found in the system, 
♦  any conductive dirt or dust has accumulated in the unit, 
♦  accumulation of dust affects heat supply and dissipation.