Справочник Пользователя для AEG 160-500kVA
Protect 8.33: Specification
Three Phase Output
MODEL
P8.33-160 P8.33-220 P8.33-330 P8.33-400 P8.33-500
N
OMINAL
RATING
(
AT
COS
0.8
LAG
)
IN
K
VA
160 220 330 400 500
RECTIFIER UNIT
Input nominal voltage 3
X
400 V (3
X
380 V, 3
X
415 V)
Input operating range (min/max)
340 V–460 V
Frequency
50/60 Hz ±10%
Input current in A at nominal load
259 357 535 649
811
Charging characteristic to IEC 478-10
IU
Nominal DC voltage
384 V
Rectifier type
- Standard
6 pulse
12 pulse
12 pulse
12 pulse
12 pulse
- Optional
12 pulse
INVERTER UNIT
DC input
384 V ± 20%
Nominal AC voltage
3x 400 V (3 x 380 V, 3 x 415 V)
Output voltage static response
< ±1%
Output voltage dynamic response
< ±2%
Recovery time
2 ms
Frequency 50/60
Hz
Frequency tolerance without mains ±0.1%
Frequency synchronisation range
±1% (±2%, ±3%)
Allowable load power factor
0.0 lag to 0.0 lead
Output phase current in A
231 318 477 578
723
Voltage wave form
sinusoidal
Voltage distortion
<3%
Crest factor
max. 3
Overload response 1 min.
150%
Overload response 10 mn.
125%
Max short circuit current
> 3 x I nom
STATIC BYPASS SWITCH
AC voltage 3
X
400 V (3
X
380 V, 3
X
415 V)
Frequency
50/60 Hz
Nominal power in kVA
160 220 330 400
500
GENERAL DATA
Efficiency (AC to AC) – typical
up to 94% / >98% with ECO-Mode
Noise level depending on rating
up to 74dB(A)
EMC compatibility
EN 62040-2
Air cooling with redundant and monitored fans
Yes
Operating temperature range min./max.
(without de-rating)
(without de-rating)
–5°C / +40°C
Storage temperature range min./max.
–30°C / +75°C
Maximum altitude without de-rating
1000 m
Protection degree IEC 529/EN 60529
standard system
standard system
IP20, IP22
& IP43 (>IP43 engineered)
Equipment colour
RAL 7035
WEIGHTS AND DIMENSIONS
Height standard UPS (mm)
1910 1915 1915 1915
1915
Height with max. options (mm)
2015 2210 2210 2210
2210
Width (mm)
1800 2100 3300 3300
3300
Depth (mm)
960 960 960 960
960
Weight (kg)
2410 2900 3970 4380
4980