Default  setting:  No  automatic  supply  for  load 
over  integrated  bypass  after  executing  step  1 
and 2 (Modification of the configuration with the 
provided Software ”CompuWatch“).
3.
Then  connect  the  outputs  of  your  UPS  to  your 
loads. Use the load connection cables provided for 
this.  Don’t  switch  on  the  loads  yet.  Please 
contact  your  dealer  if  you  require  additional  load 
connection cables.
4.
Now  switch  on  the  UPS. To  do  this,  press  and 
hold the UPS ON switch for about 2 seconds.
5.
When  being  powered  on,  the  UPS  will  perform 
self-diagnosis, the Load/Battery level LEDs will be 
turned  on  and  then  off  one  after  another  in 
ascending  order.  After  synchronising  the  inverter
successfully  the  LED  “Inverter”  will  go  on  after 
some  seconds,  with  the  UPS  in  normal  mode.  If 
the  power  supply  is  in  order  (mains  within  the 
range) an additionally the LED “Line” will go on. If 
this  LED  is  flashing,  the  phase  and  neutral  of  the 
UPS  are  exchanged.  In  this  case  turn  the  mains 
connector 180
0
 in the shockproof socket.
i
Please  shut  down  the  entire  system  if  you 
cannot  solve  any  problems  which  occur.  Press 
the OFF button for about 2 seconds. Disconnect 
the  UPS  from  the  mains  by  pulling  the  mains 
connector. Please contact our hotline (s.p. 4).
6.
When  all  displays  are  lit  as  described,  switch  on 
your loads one after the other. Note the maximum 
permitted UPS load when doing this. Keep in mind 
that  especially  loads  like  laser  printers  and  big 
CTRs  have  high  power  consumption  and  can 
cause an overload of the UPS quickly.
i
Behaviour when switching on / off:
The 
behaviour 
after 
switching 
on 
(On-
Pushbutton) or off (Off-Pushbutton) the UPS can 
be  defined  with  the  Software  “CompuWatch”: 
Activation  of  the  automatic  bypass  or  either 
deactivation (latter = factory-made presetting).