CABLE CONNECTIONS AND REQUIREMENTS
Table A shows the recommended maximum distances to wire the WCS1-4 to a Spectra or Esprit 
positioning system.
To determine the correct voltage tap:
1. Pick the unit type.
2. Find the wire gauge used (22 gauge is not recommended).
Determine which secondary output tap (A, B, or C) is appropriate for the distance between the dome or 
positioning system and the WCS1-4. 
NOTE: Distance is in feet; values in parenthesis are in meters.
Maintenance
There are no user-serviceable parts except for the fuse. If the transformer in the WCS1-4 does not work 
properly, the entire environmental power supply needs to be returned to the factory for repair. Refer to 
Warranty and Return Information located on the inside back cover of this manual for instructions on 
returning the WCS1-4.
Clean the outer surface of the WCS1-4 box with a nonabrasive cleaning cloth and antistatic cleaner. 
Do not use kerosene or similar substances that may damage the surface.
Table A.  Maximum Wiring Distance from Transformer to Load
Power Consumption 
(25 VA)
20 AWG
(0.5 mm
2
)
18 AWG
(1.0 mm
2
)
16 AWG
(1.5 mm
2
)
14 AWG
(2.5 mm
2
)
12 AWG
(4.0 mm
2
)
Tap A (24 VAC, 50/60 Hz)
113 (34)
180 (55)
287 (87)
455 (139)
725 (221)
Tap B (26 VAC, 50/60 Hz)
133 (40)
212 (64)
337 (103)
536 (163)
852 (260)
Tap C (28 VAC, 50/60 Hz)
155 (47)
246 (75)
392 (119)
623 (190)
990 (302)
Power Consumption 
(50 VA)
20 AWG
(0.5 mm
2
)
18 AWG
(1.0 mm
2
)
16 AWG
(1.5 mm
2
)
14 AWG
(2.5 mm
2
)
12 AWG
(4.0 mm
2
)
Tap A (24 VAC, 50/60 Hz)
56 (17)
90 (27)
143 (43)
228 (69)
362 (110)
Tap B (26 VAC, 50/60 Hz)
66 (20)
105 (32)
168 (51)
268 (81)
425 (129)
Tap C (28 VAC, 50/60 Hz)
77 (23)
122 (37)
195 (59)
311 (94)
493 (150)
Power Consumption 
(70 VA)
20 AWG
(0.5 mm
2
)
18 AWG
(1.0 mm
2
)
16 AWG
(1.5 mm
2
)
14 AWG
(2.5 mm
2
)
12 AWG
(4.0 mm
2
)
Tap A (24 VAC, 50/60 Hz)
41 (12)
64 (19)
102 (31)
163 (50)
259 (79)
Tap B (26 VAC, 50/60 Hz)
49 (15)
78 (24)
124 (38)
198 (60)
315 (96)
Tap C (28 VAC, 50/60 Hz)
55 (17)
88 (27)
135 (41)
222 (68)
353 (107)