Chapter  4    Tabs            7 
GXT3 Configuration Program     User Manual 
 
Figure 4-3    Options Tab 
 
Note  
In the Options Tab, the UPS must be in Standby mode for the setting to take effect. 
 
Disable output - manual restart only 
For particular industrial applications and special computer applications, the UPS may be  monitored and controlled 
using external voltages and relay contact signals. 
An Any Mode Shutdown command can be activated on the terminal block of the UPS by operating Pin1 & Pin2. 
If selected, the Disable Output 
– Manual Restart Only setting will require the UPS to be manually restarted by 
pressing the Start button on the front panel of the UPS after the Any Mode Shutdown signal on the terminal block has 
been removed. 
 
Note  
If the UPS is in a remote location with limited access then the setting should not be used.  
 
Auto-enable output automatically 
For particular industrial applications and special computer applications, the UPS may be  monitored and controlled 
using external voltages and relay contact signals. 
An An y Mode Shutdown command can be activated on the terminal block of the UPS by operating Pin1 & Pin2. 
If selected, the Auto-Enable Output Automatically setting will automatically restore the UPS output after Any Mode 
Shutdown signal on the terminal block has been removed. 
Default operation - normally open 
The shutdown logic can be configured for normally open or normally closed. This setting defines the configuration of 
the An y Mode Shutdown. 
If selected, the Any Mode Shutdown will operate when Pin1 & Pin2 of the terminal block are connected 
Inverted operation - normally closed 
The shutdown logic can be configured for normally open or normally closed. This setting defines the configuration of 
the An y Mode Shutdown. 
If selected, the Any Mode Shutdown will operate when Pin1 & Pin2 of the terminal block are disconnected. 
4.3   Battery Tab 
Select the Battery Tab, as shown in Figure 4-4.