6            Chapter 4    Tabs 
GXT3 Configuration Program    User Manual 
 
Notes 
1. For the GXT3 Dual-Inverter models, this sets the L1-N and the L2-N nominal voltage.  
2. The L1-L2 voltage is dependent upon the phase angle of the input utility and is auto-detected when power is first applied. 
3. For the GXT3 230 volt single inverter model, only those voltages supported by the UPS will be displayed. 
 
L-N reverse detection 
The L-N reverse detection is only for the 120V UPS. Proper wiring of the receptacle powering the UPS is critical for 
safety, EMI suppression, and surge suppression. The UPS checks the outlet when first plugged  in. 
 Enable L-N reverse detection is checked 
When the box of Enable L-N Re verse Detection (120V UPS only) is checked, alarm of L-N reverse will be enabled. 
If the Line-Neutral is reversed or the ground is missing, the UPS will not start.   
If a problem is detected after the UPS is started, the UPS will continue to operate, bu t the AC INPUT LED will flash. 
In this situation, the improperly wired receptacles should be immediately repaired before the UPS is put into service. 
 Enable L-N reverse detection is unchecked 
When the box of Enable L-N Re verse Detection (120V UPS only) is unchecked, alarm of L-N reverse will be 
disabled. 
Frequence selection 
The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the model. All models 
are capable of being used as 50Hz or 60Hz systems.   
 For typical applications 
Auto Sensing 
– 50 or 60Hz – Bypass Enabled or Auto Sensing – 50 or 60Hz – Bypass Disabled should be 
selected according to the application. 
The UPS will auto-sense the utility frequency when first plugged in and set the nominal frequency to match. 
 For some special applications 
For some special applications , the UPS is required to be used as a frequency converter. In this application the 
following options are available: 
Frequenc y Converter 
– 50Hz – Bypass Disabled or Frequency Converter – 60Hz – Bypass Disabled
Frequenc y Converter 
– 50Hz – Bypass Disabled mode will provide 50Hz UPS output from any qualified 
commercial power. Frequenc y Converter 
– 60Hz – Bypass Disabled mode will provide 60Hz UPS output from any 
qualified commercial power. 
 
Note  
Frequency Converter – 50Hz – Bypass Disabled or Frequency Converter – 60Hz – Bypass Disabled mode disables the 
Bypass. If, for any reason, the UPS inverter is unable to power the load, the alternate bypass to utility power will not  be available 
and power will be removed from any load.  
 
Audible alarm control 
Enable Audible Alarm Control, if checked the audible alarms are enabled. 
Enable Audible Alarm Control, if unchecked the audible alarms are disabled. 
4.2   Options Tab 
Select the Options Tab, as shown in Figure 4-3.