4            Chapter 3    Operation 
GXT3 Configuration Program    User Manual 
 
Note  
At this time, if the UPS is already ON, you do not need to restart it. 
 
Changes rejected 
When the Apply or OK button is selected to transmit new settings on the UPS Tab or Options Tab, the UPS must be 
put in the Standby mode, or the changes will be rejected, and the error message will be displayed, as shown in 
Figure 3-2. 
 
Figure 3-2    The changes are rejected 
At this point, you should put the UPS to the Standby mode. If the UPS is in Normal Mode operation, press the OFF 
button once to put the UPS into Bypass  Mode. Once the UPS is in Bypass Mode operation, press and release the 
OFF button two distinct times (for about a second each time) to place the UPS in Standby mode. 
Partial save 
If the UPS is not in the Standby mode, and changes from both the Battery Tab and the UPS Tab or Options Tab are 
selected, the UPS will only save the changes on the Battery Tab. The Partial Save message will be displayed, as 
shown in Figure 3-3. 
 
Figure 3-3    Partial save