Users Manual & Installation Guide  
                            PV- 5127: 
Power supply module with UPS 
 
 
Page 12 of 31 
 
System temperature 
The PV-5127 has a temperature measuring circuit that can control an external fan and heater, and 
prevent the CPU from starting if the temperature is too low or too high.  It monitors the system 
temperature as long as +5V STB is on. 
 
As system temperature sensor, you can use the onboard sensor, or an external sensor of type 
Infineon KTY 11-5 connected to J2 (labelled “Ext. sensor”).  If you don’t want any temperature 
control, you can also configure it to a simulated 10°C, which effectively disables the temperature 
control. 
 
The circuitry checks for four different temperature ranges: too coldcoolwarm, and too hot
 
Range 
Thresholds 
Too cold 
Below (0°C, 3°C) 
Cool 
Between (0°C, 3°C) and (15°C, 18°C) 
Warm 
Between (15°C, 18°C) and (47°C, 55°C) 
Too hot 
Above (47°C, 55°C) 
 
There is hysteresis when moving between the ranges.  The notion (0°C, 3°C) denotes the lower and 
upper hysteresis levels, so that the change from too cold to cool happens when the temperature rises 
above 3°C, but to change from cool to too cold, the temperature must fall below 0°C.  Similarly for 
the threshold between cool and warm (at 15°C and 18°C), and between warm and too hot (at 47°C 
and 55°C). 
 
For testing purposes, the too cold and too hot ranges can be simulated.  To simulate too cold, mount 
a jumper on J2 instead of a sensor.  To simulate too hot, leave both J2 and ST3 unconnected. 
 
The temperature ranges are used for these functions: 
 
Range 
CPU start 
allowed 
Heater 
Fan 
Critical alarm 
Cold 
LED 
Hot 
LED 
Too cold 
No 
On 
Off 
No 
Flashing 
Off 
Cool 
Yes 
Off 
Off 
No 
Off 
Off 
Warm 
Yes 
Off 
On 
No 
Off 
Off 
Too hot 
No 
Off 
On 
Yes 
Off 
Flashing