Users Manual & Installation Guide  
                            PV- 5127: 
Power supply module with UPS 
 
 
Page 10 of 31 
ATX connector (CN10) 
The ATX connector holds the three ATX-signals: PS_ON, PWR_GOOD and +5V Standby. 
The layout of this connector is shown in the schematic.  The function of the individual ATX signals 
is shown in the table: 
 
ATX signal 
Pin no 
Function 
GND 
System GND 
For factory use only 
For factory use only 
For factory use only 
For factory use only 
For factory use only 
+5V STB 
+5V Standby 
PWR_GOOD 
This pin is 3.3V when +5V and +12V is OK 
PS_ON 
This pin must be pulled low in order to start PV-5127 
GND 
10 
System GND 
 
Ext. sensor connector (J2) 
This connector is for an external ambient (system) temperature sensor, see section System 
temperature.  The input is designed for the Infineon KTY11-5 temperature dependent resistor 
(Infineon ordering code Q62705-K245).  Mating connector for J2 is Molex 7880-2.  A ready-made 
sensor with a 40 cm cable and connector is available as the PV-5127-TW40 accessory.  
 
Batt. sensor connector (J1) 
This connector is for an external battery temperature sensor, or a jumper, see section Battery 
monitor and charger.  The input is designed for the Infineon KTY11-5 temperature dependent 
resistor (Infineon ordering code Q62705-K245).  Mating connector for J1 is Molex 7880-2.  A 
ready-made sensor with a 40 cm cable and connector is available as the PV-5127-TW40 accessory.  
From the factory, a jumper is installed, disabling the battery temperature control. 
 
Pinheader (ST3) 
This pinheader is for configuring the System temperature measurement, see section System 
temperature.  You can mount a jumper in the “10°C” position, in the “On-board sensor” position, or 
you can leave it unconnected.  The factory default is a jumper in the “10°C” position.   
 
Jumper position (ST3) 
Input for System temperature 
No jumper installed 
Sensor connected to J2 
Jumper on ‘On-board sensor’ 
On-board sensor.  Leave J2 unconnected. 
Jumper on ‘10°C’ 
Simulate +10°C.  Leave J2 unconnected. (Factory default)