Users Manual & Installation Guide  
                            PV- 5127: 
Power supply module with UPS 
 
 
Page 20 of 31 
Battery monitor and charger 
Battery voltages 
The PV-5127 monitors the voltage of the battery as long as the main DC/DC converter is on.  The 
voltage status controls the charger, the RS232 alarm output, the battery LED, and it can be read 
through PC/104.  The possible ranges are: 
 
Range 
Thresholds 
Empty 
Below 9.5V 
Low 
Between 9.5V and (10.75V, 11.25V) 
Medium 
Between (10.75V, 11.25V) and (13.0V, 14.7V) 
Full 
Between (13.0V, 14.7V) and 15.0V 
Disconnected 
Above 15.0V 
 
There is hysteresis when moving between some of the ranges.  The notion (10.75V, 11.25V) 
denotes the lower and upper hysteresis levels, so that the change from low to medium happens when 
the voltage rises above 11.25V, but to change from medium to low, the voltage must drop below 
10.75V. 
 
When empty, and running on battery, power is immediately turned off to protect the battery against 
complete discharge.  This is the safety shutdown feature.  Empty can also mean that no battery is 
connected. 
 
When low, and running on battery, a Critical alarm is reported through RS232. 
 
The medium and full ranges control the charging mode, see below. 
 
The disconnected state happens when the charger is on, and there is no battery connected. 
 
Lead-acid charger 
The PV-5127 has an integrated lead-acid battery charger that will maintain the UPS battery as long 
as the mains voltage is present.  The battery charger has three modes of operation: Fast charge, 
trickle charge, and off
In the fast charge mode, the battery charger will deliver a constant current to the battery as long as 
the battery voltage has not reached 14.7V.  This current can be programmed by a jumper at ST1. 
 
ST1 installed 
ST1 removed 
Fast charge current=1A 
Fast charge current=0.5A 
 
After reaching 14.7V, the charger goes into trickle charge mode.  In this mode, the battery is 
supplied with a constant voltage of 13.6V.  When the battery voltage falls below 13.0V, the charger 
returns to fast charge mode. 
 
Charging a lead-acid battery while it is too hot may damage it.  The PV-5127 has an input, J1, for 
connecting an external battery temperature sensor.  The sensor, if used, should be physically