Users Manual & Installation Guide  
                            PV- 5127: 
Power supply module with UPS 
 
 
Page 19 of 31 
00h: SOFT_OFF (first half of 2-second delay) 
FEh: SOFT_ON 
FFh: SOFT_OFF (second half of 2-second delay), or SOFT_TEMPBAD 
Other values: SOFT_DELAY, delayed shutdown in progress.  value = remaining seconds until 
SOFT_OFF 
 
Software normally won’t read the values 00h and FFh since the 5V+12V is off at this time.  Writing 
00h will turn off power immediately, and it will stay off for at least two seconds.  You shouldn’t 
write FFh since this will turn power off for only one second, and this might not be enough for a 
CPU to reboot cleanly.  Writing FEh will cancel a delayed shutdown in progress.  Writing other 
values will initiate (or modify) a delayed shutdown, with the value being the number of seconds 
until SOFT_OFF. 
 
Software compatibility 
Windows NT 4.0: The PV-5127 RS232 interface is directly compatible with the Windows NT 4.0 
UPS service, using the CDB-9F cable.  It can monitor the three statuses (Normal, Mains alarm, 
Critical alarm), and use the RS232 Shutdown signal to power off. 
 
Windows 2000 and XP: The UPS service in these operating systems can monitor the three statuses 
(Normal, Mains alarm, Critical alarm) through RS232, but it cannot power off the PV-5127 with the 
Shutdown signal.  This is because the UPS service is terminated during shutdown, so it cannot 
activate the Shutdown signal when shutdown is complete. 
  
To power off the PV-5127 after a shutdown under Windows 2000 and XP, you must use either the 
PS_ON signal with an ATX compatible CPU, or the PC/104 interface.  Using the PS_ON signal 
ensures that power is turned off exactly when the operating system has finished shutting down. 
The PC/104 interface is used by the PV-5127 UPS minidriver available at 
http://www.micro-
technic.com/pv5127/
.  This method does not use an RS232 port or cable. 
 
Linux: Several UPS monitoring daemons exist which use the “simple” or “dumb” signalling 
protocol on a serial port.  Examples are: 
 
apcupsd (
http://www2.apcupsd.com
): When using the CDB-9F cable, you should specify 
UPSCABLE 940-0020B. 
 
Network UPS Tools (
http://www.networkupstools.org
): When using the CDB-9F cable, you 
should specify genericups upstype=2. 
 
Other daemons: Make sure that you use the right handshake signals since no single standard 
exists for which handshake are used for which function, and adapt either the software 
configuration or the cable accordingly. 
 
With some UPS hardware, you can experience a “deadlock” problem if mains power comes back 
after the UPS monitoring software has decided to shut down the operating system.  This happens if 
the UPS monitoring software is unable to turn off power after the operating system has finished 
shutting down, because mains power has come back.  This cannot happen with the PV-5127 
because it always turns off power for at least two seconds after a power-off command through 
RS232 or PC/104, even if mains power is present.