Users Manual & Installation Guide  
                            PV- 5127: 
Power supply module with UPS 
 
 
Page 30 of 31 
Thermal considerations 
When installing the Micronix PV-5127 in a PC/104 stack, some considerations about convection 
must be made.  For the power supply to work properly, certain temperature limits must not be 
exceeded.  Several factors will affect the temperature raise in the PV-5127: 
 
the delivered power 
 
the convection inside the cabinet 
 
the input voltage (mains) and 
 
the ambient temperature 
 
Tests have shown that if the temperature at the top of the electrolytic capacitors do not exceed 
105°C, the PV-5127 is thermally safe.  This table shows the relationship between Uin and Tcap: 
  
Uin[V] 
Tcap[°C] 
Tamb max.[°C] 
Pout[W] 
10 
67 
60 
75 
18 
72 
55 
75 
24 
74 
53 
75 
30 
86 
41 
75 
 
All figures in the table match an ambient temperature equal to 22°C without forced cooling. 
A raise in ambient temperature must be added to Tcap.  This gives the max. ambient temperature: 
Tamb max. =  (105 –Tcap) + 22.  These figures are given in the table.  
If the PV-5127 is placed in an ambient temperature that is higher than indicated in the table, the 
system integrator must arrange forced cooling.  Temperature experiments have shown that a min. 
airflow parallel to the surface of the heat sink of 0.5m/s is adequate for max. load at ambient 
temperatures up to 84°C.  For durability reasons, it is recommended not to use PV-5127 at ambient 
temperatures exceeding 70°C at full load. 
*
+,
*
*
+,
*
+,
#
$*
+,
-
.
/
/