Справочник Пользователя для Micro Technic PV-5127

Скачать
Страница из 31
Users Manual & Installation Guide  
                            PV- 5127: 
Power supply module with UPS 
 
 
Page 9 of 31 
Heater and fan control and external LEDs connector (CN2) 
Status for PV-5127 can be shown on external LEDs.  These must be connected to CN2 by a 10 
position ribbon cable with a mating connector.  Furthermore, the +5V Standby and logical outputs 
for the external heating element and the external fan are placed in this connector.  The layout of this 
connector is shown in the schematic to the left of the connector.  The function of the individual 
LEDs is shown in the table: 
 
LED name 
Pin no  Function 
GND 
System GND. 
Mode_Green_LED 
See note. 
Heat_On 
Logical output for external heat element, 3.3V when active. 
Mode_Red_LED 
See note. 
Battery_LED 
See section 
Battery monitor and charger
Mains_OK_LED 
On when mains supply OK. 
Hot_LED 
See section 
UPS control.
 
Fan_On 
Logical output for external fan, 3.3V when active. 
Cold_LED 
See section 
UPS control.
 
+5V_STB 
10 
+5V standby, is active when the main DC/DC converter is on. 
 
Note: Mode_Green_LED and Mode_Red_LED are intended for use with a two-color red+green 
LED.  When both Mode LEDs are on, you get yellow.  The possible colors are: 
 
Mode LED color 
Function 
Green 
On, both +5V and +12V are on 
Yellow 
Standby, only +5V Standby is on 
Off 
Off, main DC/DC converter is off 
 
The LEDs should be connected like this: 
 
 
RS232 connector (CN3) 
This connector is documented in the UPS Control section.