Справочник Пользователя для Mitsubishi Electronics 700 Series

Скачать
Страница из 183
25
Inverter Status Monitoring, Special Registers
for Control
1
1.7.3
How to write data by controlling (OFF to ON) the write
 command
You can write the operation mode and set frequency to the inverter, batch-clear the
alarm definitions, and clear all parameters.
The above data are written as soon as the write completion turns on after the write
command has turned from off to on.
(Alarm definition batch clear (D9146) and all parameter clear (D9147) turn on at
completion of clear.)
To write the data again, the write command must be turned off once, then on again.
Data write timing chart
Device 
No.
Name
Write 
Command
Write 
Completion
Data Access 
Enable Condition
D9143
Operation mode setting write
Y23
X23
Pr.79 =0, 2
D9144
Set frequency write (RAM)
Y24
X24
PU operation mode 
(PU LED on) or CC-
Link operation mode 
(PU and EXT LEDs 
flicker slowly)
D9145
Set frequency write 
(E
2
PROM)
Y25
X25
D9146
Alarm definition batch clear
Y26
X26
Always
D9147
All parameter clear
Y27
X27
As set in Pr. 77
X2n(n=3 to 7)
Write completion
D914n(n=3 to 7)
Write data
User data
Y2n(n=3 to 7)
Write command
1) In user sequence, user
    data is stored into write 
    data area (D914n).
2) In user sequence, write
    command is turned on.
4) After confirmation of write
    completion, write command
    is turned off.
3) Turns on when inverter CPU completes data 
    write to inverter.
    Alarm definition clear and parameter
    clear turn on at completion of clear.
    0 written to D9150 indicates normal completion.
    Any value other than 0 indicates abnormal completion.
5) Inverter CPU confirms that
    write command is off and
    turns off write completion.