Inverter Status Monitoring, Special Registers 
for Control
(1) Operation mode setting write (D9143)
Data are as follows:
The operation mode switching method is as shown below when the Pr.79
Operation mode selection
 value is "0".
When Pr. 79 =2, switching is performed as shown below.
There are no restrictions on operation mode switching.
On normal completion of operation mode setting, the write completion signal
(X23) turns on, and at the same time, 0 is set to D9150.
If the value written is other than H0000 to H0002 or write is performed during
inverter operation, HFFFF is set to D9150 as soon as the write completion signal
(X23) turns on, resulting in abnormal completion.
If abnormal completion occurs, the operation mode is not changed.
<Operation mode setting write program example>
The following program changes the operation mode to the NET mode.
Data Setting
Operation Mode
H0000
NET operation mode
H0001
External operation mode
H0002
PU operation mode
REMARKS
When Pr. 79 is other than 0, the mode is fixed.
H0001
H0000
H0002
H0001
(CC-Link)
H0002
H0000
NET mode
External
operation mode
PU operation
mode
H0001
H0000
(CC-Link)
NET mode
External 
operation mode
Operation mode write setting request
Normal write
Abnormal write
Turns on operation mode
setting write request pulse.
Check whether operation mode 
setting write completion signal
turned on to judge whether write
was performed normally or not.
Stores 0 (CC-Link operation mode)
to D9143 and turns on operation
mode setting write command. 
(Until completion signal turns on)