Power supply
The server has two hot-swap power supply module bays on the rear 
panel that accept hot-swap redundant power supply modules. The 
system ships out with two power supply modules installed. A 
redundant power configuration enables a fully-configured system to 
continue running even if one power supply module fails.
WARNING! To reduce the risk of personal injury or damage to 
the equipment, the installation of power supply modules 
should be referred to individuals who are qualified to service 
server systems and are trained to deal with equipment capable 
of generating hazardous energy levels. 
WARNING! To reduce the risk of personal injury from hot 
surfaces, observe the thermal labels on each power supply 
module. You can also consider wearing protective gloves.
WARNING! To reduce the risk of personal injury from electric 
shock hazards, do not open the power supply modules. There 
are no serviceable parts inside the module.
Caution! Electrostatic discharge can damage electronic 
components. Make sure that you are properly grounded 
before handling a power supply module.
Caution! Due to chassis airflow disruption, a power supply 
bay should never be vacant for more than two minutes when 
the server is powered on. Exceeding five minutes might cause 
the system to exceed the maximum acceptable temperature 
and possibly damage the system components. 
Caution! The system does not support running with only one 
power supply. To prevent chassis airflow disruption, a power 
supply bay should never be vacant for more than two minutes. 
Exceeding the time may cause the system to exceed the 
maximum acceptable temperature and possibly damage 
system components. 
Caution! The system operating voltage range is 200 to 240 
VDC. Do not plug the power cord into an incorrect voltage 
voltage source.