V. Removal and Replacement of Components
 WARNING
1. This unit should be diagnosed and repaired only by qualified service 
personnel to reduce the risk of death, electric shock, serious injury, or fire.
2. Move the power switch to the "OFF" position and unplug the unit from the 
electrical outlet before servicing. 
3. 
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews 
are securely in place after the unit is serviced. Make sure that none have 
fallen into the storage bin.
4. Make sure all food zones in the icemaker and storage bin are clean after 
the unit is serviced. For cleaning procedures, see "VI. Cleaning and 
Maintenance."
A. Service for Refrigerant Lines
 WARNING
1. Repairs requiring the refrigeration circuit to be opened must be performed by 
properly trained and EPA-certified service personnel.
2. Always recover the refrigerant and store it in an approved container. Do not 
discharge the refrigerant into the atmosphere.
3. Use an electronic leak detector or soap bubbles to check for leaks. Add a 
trace of refrigerant to the system (if using an electronic leak detector), and 
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-134a 
as a mixture with pressurized air for leak testing. 
CAUTION
1. Do not leave the system open for longer than 15 minutes when replacing or 
servicing parts. The Polyol Ester (POE) oils used in R-134a units can absorb 
moisture quickly. Therefore it is important to prevent moisture from entering 
the system when replacing or servicing parts.
2. Always install a new drier every time the sealed refrigeration system is 
opened. Do not replace the drier until after all other repair or replacement has 
been made.
3. When brazing, protect the drier by using a wet cloth to prevent the drier from 
overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
No refrigerant access valves are provided on this unit. Using proper refrigerant 
practices, utilize a temporary tap-line valve on the high side to recover the refrigerant. 
Store the refrigerant in an approved container. Do not discharge the refrigerant into the 
atmosphere. 
After recovery is complete, replace the tap-line valve with a proper, permanent access 
valve.