Справочник Пользователя для Traulsen TU044LT

Скачать
Страница из 16
-2-
II. GENERAL INFORMATION 
II. a-INTRODUCTION: 
This manual applies to the following models only:  
TU Series Full-Size Undercounter Refrigerators
TU044HT, TU072HT & TU100HT
TU Series Full-Size Undercounter Freezers
TU044LT & TU072LT
II. b-MODEL DESIGNATIONS:  
                   TU 044 HT
Positions
        1    2     3
Position 1: 
TU = Traulsen Undercounter
Position 2: 
044 = 44”   Length Model
 
 
072 = 72”   Length Model
 
             100 =100”  Length Model
Position 3: 
HT=Refrigerator
 
 
LT=Freezer
II. c-WIRING DIAGRAM:
Refer  to  the  wiring  diagram  for  any  service  work  per-
formed on this unit.  A copy is placed on the unit when 
shipped.  Also, a copy of the wiring diagram is located on
 
page 7 of this manual.  Should you require another copy, 
or a wiring diagram for an older production unit, please 
contact Traulsen Service at (800) 825-8220.  You should 
have model and serial number of unit prior to calling.  See 
page 1 for serial tag location and information.
II. d-INSTALLATION:
Generally TU Series Full Size Undercounter refrigerators 
and  freezer  units  are  installed  by  the  dealer,  or  other 
parties contracted by the dealer or owner.  Detailed in-
stallation instructions are included along with each unit 
when shipped.
  
II. e-CLEANING:
Detailed cleaning instructions are included with each unit, 
however special care 
MUST be given to the condenser 
coil.  The condenser coil must be cleaned at a minimum 
of every six months.  This can be done with a vacuum 
cleaner using a brush attachment, or a stiff brush or whisk 
broom.  For more information on cleaning, please refer 
to the Owner’s Manual.
II. f-TOOL REQUIREMENTS: 
For most jobs a standard set of hand tools, a VOM and 
AC current tester, along with a temperature tester or ther-
mometer are adequate tools.  However, in some cases 
the following additional tools may be required as well:
II. f-TOOL REQUIREMENTS (cont’d): 
●  Refrigeration Guage Manifold
●  Refrigeration Reclaiming Equipment
●  Acetylene Torch
●  Anti-Static Grounding Kit (TL 84919)
●  Nitrogen Bottle With Gauges
●  Thin 5/16” Open End Wrench
●  Refrigerant Reclaim Unit
II. g-REFRIGERATION SYSTEM-THEORY OF 
       OPERATION:  
The  refrigeration  system  is  the  mechanism  whereby  heat  is 
transferred from the cabinet to the outside air.  It works under 
the principle that the heat moves from hot to cold as it tries to 
establish equilibrium.
The microprocessor control signals a need for heat to be removed 
from the cabinet.  The compressor begins by compressing the re-
frigerant gas as it is discharged.  The high pressure refrigerant 
now circulates through the condenser, removing heat from the 
refrigerant and condensing it into a  liquid.  From there the refrig-
erant flows to the filter drier which removes all traces of moisture 
and particles from the system.  
After the filter drier, the refrigerant passes through a “metering 
device”. Traulsen uses a thermostatic expansion valve to regulate 
the flow of refrigerant into the evaporator coils. 
In the evaporator coil, heat is transferred from the cabinet to the 
refrigerant, which changed from a cold liquid to a warm low pres-
sure gas.  When the desired cabinet air temperature has been 
reached, the microprocessor control shuts off the compressor.  
See figure 2.
II. h-AIR FLOW REQUIREMENTS:
To  assure  optimum  performance,  the  condensing  unit  of  your 
Traulsen  unit 
MUST  have  an  adequate  supply  of  air  for  cool-
ing  purposes.    Therefore,  the  operating  location  must  allow  a 
minimum  of  12”  clearance  in  front  of  the  louvers  to  allow  for 
unrestricted air flow to the condensing unit.
Figure 2