FINAL CHECK LIST 
A. 
Check operating pressures. 
 
B. 
Check electrical requirements of unit to supply voltage. 
 
C. 
Set temperature control for desired temperature range. 
 
D. 
Check system for proper defrost settings and operation. 
 
E. 
Check condensing unit for vibrating or rubbing tubing.  Dampen and clamp as required. 
 
F. 
All valves should be completely open counter-clockwise. 
 
G. 
Check packing nuts on all service valves. 
 
H. 
Replace all service valve caps and latch unit covers. 
 
SENSOR PROBE  
 
NOTICE:  If the probe assembly is disconnected from the main board during normal operation (unit running), 
the connectors must be installed in the same position that they had before disconnection (P1 and P2), 
otherwise the control will not function properly. 
 
The Electronic  Refrigeration Control sensors  have NTC thermistors.  The reference resistance is 30,000 
ohms at 77
°F (25°C).  It carries NTC thermistors with a range of –40° to 199° F.   In case there is a failure, 
these sensors should be used in replacement of the sensors shipped with the control.  In order to diagnose 
faults in the probe, the control has LED functions as a diagnostic tool.  When power is supplied to the control, 
the LED will turn on and will remain on as long as this condition is satisfied.  When there is a fault in the probe, 
the LED will blink intermittently.  When this occurs, the probe assembly needs to be replaced.  If power is 
supplied to the control and the LED remains off, there is a failure in the main relay control and it needs to be 
replaced. 
 
In case of a probe failure, the control will go into a safety mode of operation.  While in safety mode the control 
ignores probe inputs and cycles the compressor on for 5 minutes and off for 3 hours.  The LED will be blinking 
and signaling that  there is something wrong with the probe.  To replace the sensor probes, disconnect power 
to the control, replace the probes and restart the unit.  Since the wire is fixed to the cabinet, a technician may 
cut the sensor wire inside the cabinet and splice it with a new sensor.   
 
SENSOR PROBE TEMPERATURE AND RESISTANCE 
Temperature Resistance 
°
°
Ohms 
-29.2 -34 
683,100 
-20.2 
-29 
499,200 
-9.4 -23 
347,100 
-0.4 
-18 
259,500 
10.4 -12 
185,200 
19.4 
-7 
141,200 
30.2 -1 
103,100 
32.0 
97,950 
39.2 4 
80,040 
50.0 
10 
59,700 
60.8 16 
45,000 
69.8 
21 
35,820 
80.6 27 
27,500 
89.6 
32 
22,210