Attach to Network Device Control 
On the Service menu, one of the selections is ATTACH TO NETWORK DEVICE. This table 
serves the following purposes:
to upload the Occupancy Schedule Number (if changed) for OCCPC03S, as defined 
in the Service01 table
to attach the LID to any CCN device, if the machine has been connected to a CCN 
Network. This may include other PIC controlled chillers.
to change to a new PSIO or LID module or upgrade software. 
 illustrates the ATTACH TO NETWORK DEVICE table. The Local description is 
always the PSIO module address of the machine the LID is mounted on. Whenever the 
controller identification of the PSIO is changed, this change is reflected on the bus and address 
for the LOCAL DEVICE of the ATTACH TO DEVICE screen automatically. See 
Whenever the ATTACH TO NETWORK DEVICE table is entered, the LID erases information 
on the module to which it was attached in order to make room for another device. Therefore, it is 
then required to attach to a CCN module when this screen is entered, even if the LID is attached 
back to the original module. When the ATTACH softkey is pressed, the message ‘‘UPLOADING 
TABLES, PLEASE WAIT’’ flashes. The LID will then upload the highlighted device or module. If 
the module address cannot be found, the message ‘‘COMMUNICATION FAILURE’’ will appear. 
The LID will then revert back to the ATTACH TO DEVICE screen. The upload process time for 
various CCN modules is different for each module. In general, the uploading process will take 3 
to 5 minutes.