Certain conditions during shutdown will change this sequence:
if the 
COMPRESSOR MOTOR LOAD is greater than 10% after shutdown, or the 
starter contacts remain energized, the oil pump and chilled water pump remain ener-
gized and the alarm is displayed
if the 
ENTERING CONDENSER WATER temperature is greater than 115 F (46 C) at 
shutdown, the condenser pump will be deenergized after the 1CR compressor start 
relay
if the machine shuts down due to low refrigerant temperature, the chilled water pump 
will stay running until the 
LEAVING CHILLED WATER is greater than CONTROL 
POINT, plus 5° F (3° C)
Automatic Soft Stop Amps Threshold 
The SOFT STOP AMPS THRESHOLD closes the guide vanes of the compressor 
automatically when a non-recycle, non-alarm stop signal occurs before the compressor motor is 
deenergized. 
If the STOP button is pressed, the guide vanes close to a preset amperage percent or until 
the guide vane is less than 2% open. The compressor will then shut off. 
If the machine enters an alarm state or if the compressor enters a RECYCLE mode, the 
compressor will be deenergized immediately. 
To activate SOFT STOP AMPS THRESHOLD, view the bottom of Service1 table. Set the 
SOFT STOP AMPS THRESHOLD value to the percentage amps at which the motor will shut 
down. The default setting is 100% amps (no Soft Stop).