When the SOFT STOP AMPS THRESHOLD is being applied, a status message 
‘‘SHUTDOWN IN PROGRESS, COMPRESSOR UNLOADING’’ is shown.
Chilled Water Recycle Mode
The machine may cycle off and wait until the load increases to restart again when the 
compressor is running in a lightly loaded condition. This cycling of the chiller is normal and is 
known as recycle. A recycle shutdown is initiated when any of the following conditions are true: 
when in LCW control, the difference between the 
LEAVING CHILLED WATER tem-
perature and 
ENTERING CHILLED WATER temperature is less than the RECYCLE 
SHUTDOWN DELTA T (found in the SERVICE 1 table) and the LEAVING CHILLED 
WATER TEMP is below the CONTROL POINT, and the CONTROL POINT has not 
increased in the last 5 minutes
when 
ECW CONTROL OPTION is enabled, the difference between the ENTERING 
CHILLED WATER temperature and the LEAVING CHILLED WATER temperature is 
less than the 
RECYCLE SHUTDOWN DELTA T (found in the SERVICE 1 table) and 
the 
ENTERING CHILLED WATER TEMPERATURE is below the CONTROL POINT, 
and the 
CONTROL POINT has not increased in the last 5 minutes 
when the 
LEAVING CHILLED WATER temperature is within 3° F (2° C) of the BRINE 
REFRIG TRIPPOINT 
When the machine is in RECYCLE mode, the chilled water pump relay remains energized so 
that the chilled water temperature can be monitored for increasing load. The recycle control 
uses 
RECYCLE RESTART DELTA T to check when the compressor should be restarted. This