RLA by manually overriding the guide vane target value on the LID and setting the chilled 
water set point to a low value. Do not exceed 105% of the nameplate RLA. 
3. When a steady motor current value in the desired range is met, compare the compressor 
motor amps value on the Status01 screen to the actual amps shown on the ammeter on the 
starter. Adjust the amps value on the LID to the actual value seen at the starter if there is a 
difference. Highlight the amps value then press SELECT. Press INCREASE or DECREASE 
to bring the value to that indicated on the ammeter. Press ENTER when equal. 
4. Make sure that the target guide vane position is released into AUTOMATIC mode.
To Prevent Accidental Start-Up
The PIC can be set up so that start-up of the unit is more difficult than just pressing the 
LOCAL or CCN softkeys during machine service or when necessary. By accessing the 
Status01 screen, and highlighting the chiller Start/Stop line, the value can be overridden to stop 
by pressing SELECT and then the STOP and ENTER softkeys. ‘‘SUPVSR’’ will appear after the 
value. When attempting to restart, remember to release the override. The default machine 
message line will also state that the Start/Stop has been set to ‘‘Start’’ or ‘‘Stop’’ when the value 
is overridden.