Before operation
4.3.2
Overheat protection of the motor by the inverter (Pr. 9)
Set the rated motor current in Pr. 9 Electronic thermal O/L relay to protect the motor from overheat.
Parameter 
Number
Name
Initial Value
Setting Range 
Description
9
Electronic thermal O/L relay
Inverter rated 
current 
0 to 500A
Set the rated motor current.
*1
Refer to page 182 for the rated inverter current value.
*2
The minimum setting increments are 0.01A. 
Changing example
Change the Pr. 9 Electronic thermal O/L relay setting to 22A according to the motor rated current. 
(FR-A721-5.5K)
REMARKS
· Since a thermal protector is provided for a vector control dedicated motor (SF-V5RU), set "0" in Pr. 9.
CAUTION
· Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid
unnecessary reset and power-OFF.
· When two or more motors are connected to the inverter, they cannot be protected by the electronic thermal relay function.
Install an external thermal relay to each motor.
· When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics of
the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay.
· A special motor cannot be protected by the electronic thermal relay function. Use an external thermal relay.
· PTC thermistor output built-in the motor can be input to the PTC signal (AU terminal). For details, refer to Chapter 4 of 
 the
Instruction Manual (Applied).
"         ". (22A)
5.
Press          to show the present 
     set value.
3.
Press         to choose the parameter 
     setting mode.
Flicker
 
··· 
Parameter setting complete!!
7.
Press         to set.
·
 Press         to show the setting again.
·
 Press         twice to show the next parameter.
·
 By turning          , you can read another parameter.
4.
Turn           until 
Pr. 9 Electronic 
     thermal O/L relay appears.
6.
Turn           to change the set value
      to 
1.
Screen at power-ON
     The monitor display appears.
2.
Press         to choose PU operation 
     mode.
PU indicator is lit.
The parameter number 
read previously appears.
Display
Operation
(24A for FR-A721-5.5K)
Refer to page 
182 
for initial 
value of the 
inverter rated 
current.