Precautions for maintenance and 
inspection
* Values in parentheses indicate those for 400V class.
*Consult us for periodic inspection.
6.5.7
Replacement of parts
The inverter consists of many electronic parts such as semiconductor devices.
The following parts may deteriorate with age because of their structures or physical characteristics, leading to
reduced performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.
Display
Display
(1) Check for LED lamp 
blown.
(2) Clean.
"
"
(1) Lamps indicate 
indicator lamps on 
panel.
(2) Clean with rag.
(1) Check that lamps 
are lit.
Meter
Check that reading is 
normal.
"
Check the readings of 
the meters on the panel.
Must satisfy 
specified and 
management 
values.
Voltmeter, 
ammeter, etc.
Motor
General
(1) Check for unusual 
vibration and noise.
(2) Check for unusual 
odor.
"
"
(1) Auditory, sensory, 
visual checks.
(2) Check for unusual 
odor due to 
overheat, damage, 
etc.
(1), (2) No fault.
Insulation 
resistance
Check with megger 
(across terminals and 
earth (ground) 
terminal).
"
Disconnect cables from 
U, V, W (including motor 
cables).
5M
Ω 
or more.
500V megger
Part Name
Standard Replacement Interval
Description
Cooling fan
2 to 3 years
Replace (as required)
Main circuit smoothing capacitor
10 years
Replace (as required)
On-board smoothing capacitor
10 years
Replace the board (as required).
Relays 
Replace as required.
CAUTION
For parts replacement, consult the nearest Mitsubishi FA Center.