Operation selection function 2 (Pr. 65 to Pr. 79)
P
A
RAMETERS
3
3.11.7 Reverse rotation prevention selection (Pr. 78 
)
<Setting>
3.11.8 Operation mode selection (Pr. 79
)
This function can prevent any reverse rotation fault resulting from the mis-input of the start signal.
POINT
Used for a machine that runs only in one direction, e.g. fan, pump.
(The setting of this parameter is valid for combined operation, PU operation, external operation and 
communication operation.)
Parameter
Name
Factory Setting
Setting Range
Remarks
78
Reverse rotation prevention 
selection
0
0, 1, 2
Extended mode
Control 
Method
Pr. 78 Setting
Start Signal
Limit on Analog Reversible
STF
STR
Speed 
control
V/F control
0
Valid
Valid
Negative input starts rotation in the direction 
opposite to that of start signal
1
(reverse rotation lock)
Valid
Invalid
Negative input does not start rotation.
2
 (forward rotation lock)
Invalid
Valid
Torque
control
0
Valid
Valid
Negative input starts rotation in the direction 
opposite to that of start signal
1
(reverse rotation lock)
Valid
Invalid
Negative analog input results as follows.
2
 (forward rotation lock)
Invalid
Valid
Position
control
0
Functions as a stroke signal 
and motor does not rotate in 
the direction where the STF or 
STR signal does not exist.
Under position control, analog command is 
irrelevant to the forward/reverse rotation lock 
function as it does not function in other than torque 
limit setting (absolute value used for operation).
1
(reverse rotation lock)
Motor does not rotate in the 
reverse rotation direction.
2
 (forward rotation lock)
Motor does not rotate in the 
forward rotation direction.
Used to select the operation mode of the inverter.
The inverter can be run from the control panel or parameter unit (PU operation), with external signals 
(external operation), or by combination of PU operation and external operation (external/PU combined 
operation).
The external operation mode is selected at power on (factory setting).
Parameter
Name
Factory Setting
Setting Range
79
Operation mode selection
0
0 to 4, 6 to 8
speed
torque
position
Speed
Operation
Starting speed or less
No rotation
When rotation is in the 
same direction as that of 
start signal and speed is 
higher than starting speed
Torque in the 
direction opposite to 
that of start signal is 
generated.
speed
torque
position