Terminal assignment functions (Pr. 180 to Pr. 195)
3.20.2 Output terminal function selection
 
(Pr. 190 to Pr. 192, Pr. 195
)
<Setting>
Refer to the following table and set the parameters.
You can change the functions of the open collector output terminal and contact output terminal.
Parameter
Name
Factory-
Set Value
Factory-Set Signal Function
Setting Range
Remarks
190
DO1 terminal 
function selection
0
RUN (Inverter running)
0 to 8, 10 to 16, 
20, 25 to 27, 30 
to 37, 39, 40 to 
44, 96 to 99, 
100 to 108, 110 
to 116, 120, 125 
to 127, 130 to 
137, 139, 140 to 
144, 196 to 199, 
9999
Extended mode
191
DO2 terminal 
function selection
1
SU (Up to speed)
192
DO3 terminal 
function selection
2
IPF (Instantaneous power failure/
undervoltage)
195
ABC terminal 
function selection
99
A, B, C (Alarm output)
Setting
Signal 
Name
Function
Operation
Related 
Parameters
Response 
Time
Positive 
logic
Negative 
logic
0
100
RUN Inverter running
This signal is output during operation when the inverter output 
speed rises to or above the starting speed.
During DC injection brake, 0 speed control or servo lock, this 
signal is not output. However, LX is output as ON under position 
control.
Within 
20ms
1
101
SU
Up to speed
Refer to Pr. 41 "up-to-speed sensitivity" (page 95). (Caution 1)
2
102
IPF
Instantaneous power 
failure or 
undervoltage
Output at occurrence of an instantaneous power 
failure or undervoltage.
3
103
OL
Overload alarm
Output when torque or speed limit is activated.
For V/F control, this signal is output while the stall 
prevention function is activated.
Pr. 22, Pr. 806, 
Pr. 807, Pr. 812 
to Pr. 817
4
104
FU
Output speed 
detection
Refer to Pr. 42, Pr. 43, Pr. 50 and Pr. 116 (speed detection)
 
 (page 95).
Within 
20ms
5
105
FU2 Second output speed 
detection
6
106
FU3 Third output speed 
detection
7
107
RBP Regenerative brake 
prealarm
Output when 85% of the regenerative brake duty 
set in Pr. 70 is reached.
Pr. 70
8
108
THP
Electronic thermal 
relay function 
prealarm
Output when the electronic thermal relay function 
cumulative value reaches 85% of the preset level. Pr. 9
10
110
PU
PU operation mode
Output when the PU operation mode is selected.
Within 
20ms
11
111
RY
Inverter operation 
ready
Output when the inverter can be started by 
switching the start signal on or while it is running.
12
112
Y12 Output current 
detection
Refer to Pr. 150 and Pr. 151 
 
(output current detection).
Pr. 150, Pr. 151
13
113
Y13 Zero current 
detection
Refer to Pr. 152 and Pr. 153 
 
(zero current detection).
Pr. 152, Pr. 153
14
114
FDN PID lower limit
Refer to Pr. 128 to Pr. 134 (PID control).
Pr. 128 to 
 
Pr. 134
Within 
20ms
15
115
FUP PID upper limit
16
116
RL
PID forward-reverse 
rotation output
20
120
BOF Brake opening 
request
Refer to Pr. 278 to Pr. 285 
 
(brake sequence function).
Pr. 278 to 
 
Pr. 285
25
125
FAN Fan fault output
Output at the time of a fan fault.
Pr. 244
26
126
FIN
Fin overheat 
prealarm
Output when the heatsink temperature reaches 
about 85% of the fin overheat protection activating 
temperature.
27
127
ORA Orientation in-position When orientation is valid
(Refer to page 159)
speed
torque
position