152
Terminal assignment functions (Pr. 180 to Pr. 195)
3.20.2 Output terminal function selection
(Pr. 190 to Pr. 192, Pr. 195
)
<Setting>
Refer to the following table and set the parameters.
You can change the functions of the open collector output terminal and contact output terminal.
Parameter
Name
Factory-
Set Value
Factory-Set Signal Function
Setting Range
Remarks
190
DO1 terminal
function selection
function selection
0
RUN (Inverter running)
0 to 8, 10 to 16,
20, 25 to 27, 30
20, 25 to 27, 30
to 37, 39, 40 to
44, 96 to 99,
100 to 108, 110
to 116, 120, 125
to 127, 130 to
137, 139, 140 to
144, 196 to 199,
144, 196 to 199,
9999
Extended mode
191
DO2 terminal
function selection
function selection
1
SU (Up to speed)
192
DO3 terminal
function selection
function selection
2
IPF (Instantaneous power failure/
undervoltage)
undervoltage)
195
ABC terminal
function selection
function selection
99
A, B, C (Alarm output)
Setting
Signal
Name
Function
Operation
Related
Parameters
Response
Time
Positive
logic
Negative
logic
0
100
RUN Inverter running
This signal is output during operation when the inverter output
speed rises to or above the starting speed.
During DC injection brake, 0 speed control or servo lock, this
signal is not output. However, LX is output as ON under position
control.
Within
20ms
1
101
SU
Up to speed
Refer to Pr. 41 "up-to-speed sensitivity" (page 95). (Caution 1)
2
102
IPF
Instantaneous power
failure or
undervoltage
Output at occurrence of an instantaneous power
failure or undervoltage.
⎯
⎯
3
103
OL
Overload alarm
Output when torque or speed limit is activated.
For V/F control, this signal is output while the stall
prevention function is activated.
Pr. 22, Pr. 806,
Pr. 807, Pr. 812
to Pr. 817
4
104
FU
Output speed
detection
Refer to Pr. 42, Pr. 43, Pr. 50 and Pr. 116 (speed detection)
(page 95).
Within
20ms
5
105
FU2 Second output speed
detection
6
106
FU3 Third output speed
detection
7
107
RBP Regenerative brake
prealarm
Output when 85% of the regenerative brake duty
set in Pr. 70 is reached.
Pr. 70
⎯
8
108
THP
Electronic thermal
relay function
prealarm
Output when the electronic thermal relay function
cumulative value reaches 85% of the preset level. Pr. 9
10
110
PU
PU operation mode
Output when the PU operation mode is selected.
⎯
Within
20ms
11
111
RY
Inverter operation
ready
Output when the inverter can be started by
switching the start signal on or while it is running.
12
112
Y12 Output current
detection
Refer to Pr. 150 and Pr. 151
(output current detection).
Pr. 150, Pr. 151
⎯
13
113
Y13 Zero current
detection
Refer to Pr. 152 and Pr. 153
(zero current detection).
Pr. 152, Pr. 153
14
114
FDN PID lower limit
Refer to Pr. 128 to Pr. 134 (PID control).
Pr. 128 to
Pr. 134
Within
20ms
15
115
FUP PID upper limit
16
116
RL
PID forward-reverse
rotation output
20
120
BOF Brake opening
request
Refer to Pr. 278 to Pr. 285
(brake sequence function).
Pr. 278 to
Pr. 285
⎯
25
125
FAN Fan fault output
Output at the time of a fan fault.
Pr. 244
⎯
26
126
FIN
Fin overheat
prealarm
Output when the heatsink temperature reaches
about 85% of the fin overheat protection activating
temperature.
⎯
⎯
27
127
ORA Orientation in-position When orientation is valid
(Refer to page 159)
⎯
⎯
speed
torque