154
Auxiliary function (Pr. 244)
3.21 Auxiliary function (Pr. 244)
3.21.1 Cooling fan operation selection (Pr. 244
)
<Setting>
3.22 Stop selection function (Pr. 250)
3.22.1 Stop selection (Pr. 250
)
You can control the operation of the cooling fan built in the inverter.
Parameter
Name
Factory Setting
Setting 
Range
Remarks
244
Cooling fan operation 
selection
0
0, 1
Extended mode
Setting
Description
0
Operated with power on (independently of whether the inverter is running or at a 
stop).
1
Cooling fan on-off control valid
(The cooling fan is always on while the inverter is running. During a stop, the 
inverter status is monitored and the fan switches on-off according to temperature.)
REMARKS
In either of the following cases, fan operation is regarded as faulty, [FN] is shown on the control panel, and the fan fault (FAN) 
and minor fault (LF) signals are output. Use Pr. 190 to Pr. 192, Pr. 195 (output terminal function selection) to allocate the 
terminals used to output the FAN and LF signals.
1. Pr. 244 = "0"
 
When the fan comes to a stop with power on.
2. Pr. 244 = "1"
 
When the fan comes to a stop during the fan ON command while the inverter is running.
CAUTION
Changing the terminal function using any of Pr. 190 to 192 and Pr. 195 may affect the other functions. 
Confirm the functions of the corresponding terminals before making setting.
Used to select the stopping method (deceleration to a stop or coasting) when the start signal (STF/STR) turns 
off.
Parameter
Name
Factory Setting
Setting Range
Remarks
250
Stop selection
9999
0 to 100s, 9999
Extended mode
speed
torque
position
speed
torque