Справочник Пользователя для Mitsubishi Electronics FR-V540-1.5K to 55K

Скачать
Страница из 232
155
Operation selection function (Pr. 251)
P
A
RAMETERS
3
(1) Pr. 250 = "9999"
When the start signal turns off, the motor is decelerated to a stop.
(2) Pr. 250 = other than "9999" (Output is shut off after preset time)
The output is shut off when the time set in Pr. 250 has elapsed after the start signal had turned off. The motor coasts 
to a stop.
3.23 Operation selection function (Pr. 251)
3.23.1 Output phase failure protection selection (Pr. 251
)
CAUTION
1. The RUN signal turns off when the output stops.
2. When the start signal is turned on again during motor coasting, the motor starts at 0Hz.
3. The output speed becomes the speed limit value during torque control.
You can disable the output phase failure protection (E.LF) function that will stop the inverter output if any of 
the three phases (U, V, W) on the inverter output side (load side) opens.
Parameter
Name
Setting 
Range
Minimum 
Setting 
Increments
Factory Setting
Description
Remarks
251
Output phase 
failure protection 
selection
0, 1
1
1
0: Without output 
phase failure 
protection
1: With output phase 
failure protection
Extended mode
Time
(r/min)
ON
OFF
Start signal
Decelerated when start signal turns off.
Deceleration time (time set in Pr. 8, etc.)
DC brake
Output 
speed
OFF
Start signal
Output is shut off when the preset time has 
elapsed after start signal had turned off.
Pr.250
Motor coasts to a stop.
Time
OFF
RUN signal
(r/min)
Output 
speed
speed
torque
position