Operation selection at power failure and 
instantaneous power failure
4.13 Operation selection at power failure and instantaneous 
power failure
4.13.1 Automatic restart after instantaneous power failure/flying start under general-
purpose motor control (Pr. 57, Pr. 58, Pr. 162 to Pr. 165, Pr. 299, Pr. 611) 
<V/F><S MFVC>
Purpose
Parameter that must be Set
Refer to Page
At instantaneous power failure 
occurrence, restart inverter without 
stopping motor (general-purpose 
motor control)
Automatic restart operation 
after instantaneous power 
failure / flying start
Pr. 57,  Pr. 58,  Pr. 162 to Pr. 165, 
Pr. 299, Pr. 611
At instantaneous power failure 
occurrence, restart inverter without 
stopping motor (IPM motor control)
Automatic restart operation 
after instantaneous power 
failure / flying start
Pr. 57,  Pr. 162, Pr. 611
When undervoltage or a power 
failure occurs, the inverter can be 
decelerated to a stop.
Power failure-time 
deceleration-to-stop 
function
Pr. 261 to Pr. 266
You can restart the inverter without stopping the motor in the following cases.
⋅ when bypass operation is switched to inverter operation
⋅ when power comes back ON after an instantaneous power failure
⋅ when motor is coasting at start
Parameter 
Number
Name
Initial Value
Setting Range
Description
57
Restart coasting 
time
9999
0
1.5K or 
lower ......................................... 0.5s
2.2K to 7.5K............................................ 1s
11K to 55K  ............................................. 3.0s
75K or higher .......................................... 5.0s
The above times are coasting time.
55K or lower
0.1 to 
5s
Set the waiting time for inverter-triggered restart 
after an instantaneous power failure.
75K or 
higher
0.1 to 
30s
9999
No restart
58
Restart cushion 
time
1s
0 to 60s
Set a voltage starting time at restart.
162
Automatic 
restart after 
instantaneous 
power failure 
selection
0
0
With frequency search
1
Without frequency search (Reduced voltage 
system)
10
Frequency search at every start
11
Reduced voltage system at every start
163
First cushion 
time for restart
0s
0 to 20s
Set a voltage starting time at restart.
Consider using these parameters according to the 
load (moment of inertia, torque) magnitude.
164
First cushion 
voltage for 
restart
0%
0 to 100%
165
Stall prevention 
operation level 
for restart
120%
0 to 150%
Considers the rated inverter current as 100% and 
set the stall prevention operation level during 
restart operation.
299
Rotation 
direction 
detection 
selection at 
restarting
9999
0
Without rotation direction detection
1
With rotation direction detection
9999
When Pr. 78 = "0", the rotation direction is detected.
When Pr. 78 = "1","2", the rotation direction is not 
detected.
611
Acceleration 
time at a restart
55K or lower
5s
0 to 3600s, 9999
Set the acceleration time to reach 
Pr. 20
 
Acceleration/deceleration reference frequency at a 
restart.
Acceleration time for restart is the normal acceleration 
time (e.g. Pr. 7) when "9999" is set.
75K or 
higher
15s
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
V/F
V/F
V/F
S
 MFVC
S
 MFVC
S
 MFVC