APPENDIX 7    CABLE MANUFACTURING DRAWINGS 
Appendix 7.15    FCUA-R220 Cable Manufacturing Drawing 
 
 
I - 100 
Appendix 7.15  FCUA-R220 Cable Manufacturing Drawing 
 
Application: 
Supply of 24V to control unit,   
remote I/O unit and communication terminal 
 
Option (Compatible connector set)   
FCUA-CN220 
(Note that this corresponds only to the 
connector on the control unit side.) 
 
List of parts used 
 
4
FG
GND
+24V
R220 
 
Note (3) 
R220 
Assembly drawing
No.
Part 
name/model 
Maker Q'ty
Connector 
2-178288-3 
Tyco 
Electronics 
AMP 
Contact 
1-175218-5 
Tyco 
Electronics 
AMP 
Wire material 
JPVV-SB 
1P × 0.5mm
2
 
BANDO 
Electric 
Industry 
Note (1) 
(1)
Crimp terminal 
V1.25-3 
J. S. T 
 
 
WHITE
BROWN
Maximum cable length: 30m
FG 
GND 
+24V 


FG 
GND 
+24V 
Connection diagram 
 
 
Manufacturing precautions   
(1)  The wire material shall be a shielded 1-pair stranded cable equivalent to AWG20 (0.5mm
2
).  
If the cable is 10m or longer, select AWG16 (1.25mm
2
) material or equivalent. 
(2)  The parts used shall be Mitsubishi recommended parts. Equivalent parts may be used providing 
they are compatible with the specifications. 
(3)  Attach the nameplate (with protective cover stamped with the cable name) in the position 
designated in the assembly drawing.   
(4)  Install each crimp terminal side after stamping the name of each signal on the mark tube. 
(5)  Protect both ends of the wire material with insulation bushing. 
(6)  Use AWG18 (0.75mm
2
) or equivalent for the shield treatment wire material.