Справочник Пользователя для LSI AP1172-E1

Скачать
Страница из 70
72-Inch Cabinet Site Preparation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8
Command Module and Drive Module Site Preparation Guide
Power Requirements
This section provides information regarding power requirements, AC power distribution 
box specifications, ladder cord and power cord routing instructions, and site wiring 
conditions.
The AC power source must provide the correct voltage, current, and frequency specified 
on the manufacturer’s nameplate. 
 shows the internal AC power requirements for 
rackmount cabinets.
Table  1-3    Power Requirements
Unit/Component
Requirements
Domestic International
AC Power
250 VAC, 30 A
230 VAC, 32 A
AC Plug
NEMA L6-30P, locking plug
IEC 309 locking plug
Receptacle
6-30R, receptacle
IEC 309 receptacle
Circuit Breaker
25 A
Voltage Range
180 to 257 VAC
Frequency
49 to 50.5 Hz or 59 to 60.6 Hz
Current
(specified frequency)
220 VAC, 50/60 Hz
Configuration A
1
Configuration B
1
Configuration C
1
Operational Current
LP Drives
2
7.35 A
14.70 A
13.16 A
HH Drives
2
7.70 A
15.40 A
13.72 A
Surge Current
LP Drives
10.95 A
21.90 A
22.20 A
HH Drives
11.45 A
22.90 A
23.00 A
1
Power specifications for three configurations containing Low-Profile (LP) and Half-Height (HH) drives, including:
Configuration A contains 1 command module and 5 drive modules
Configuration B contains 2 command modules and 10 drive modules
Configuration C contains 3 command modules and 8 drive modules
2
LP drives are 1.0 inch tall; HH drives are 1.6 inches tall.