Справочник Пользователя для LSI AP1172-E1

Скачать
Страница из 70
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8
Command Module and Drive Module Site Preparation Guide
Power Requirements
This section provides information regarding drive module AC power requirements, power 
cord routing instructions, and site wiring conditions.
The AC power source must provide the correct voltage, current, and frequency specified 
on the manufacturer’s nameplate. Internal AC power units for rackmount cabinets must 
be able to handle the power requirements for these units. Refer to 
 for more information. 
Table  3-7    FC-1 10x Drive Module Power Requirements
Item
Unit of Measure
Requirement
Circuit Breaker
Slow-blow Fuse
10 A per Power Supply
AC Power
Low Range
High Range
Nominal Voltage
90 to 136 VAC
198 to 264 VAC
Frequency
50 to 60 Hz
50 to 60 Hz
Idle Current 
3.02 A
1.31 A
1
Maximum Operating Current
3.11 A
1.34 A
1
Maximum Surge Current
(10-drive spin up)
4.70 A
1.92 A
1
1
Typical current: 240 VAC, 60 Hz at 0.70 power efficiency, 0.99 power factor.
Table  3-8    FC-1 14x Drive Module Power Requirements
Item
Unit of Measure
Requirement
Circuit Breaker 
Slow-blow Fuse
10 A per Power Supply
AC Power 
Low Range
High Range
Nominal Voltage
90 to 136 VAC
198 to 264 VAC
Frequency
50 to 60 Hz
50 to 60 Hz
Idle Current
2.95 A
1
1.42 A
2
Maximum Operating Current
3.03 A
1
1.46 A
2
Maximum Surge Current
(14-drive spin up)
4.28 A
1
1.97 A
2
1
Typical current: 115 V AC, 60 Hz at 0.72 power efficiency, 0.99 power factor.
2