Справочник Пользователя для LSI AP1172-E1

Скачать
Страница из 70
 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Power Requirements
Command Module and Drive Module Site Preparation Guide
3-9
Power Cord Routing
All modules are shipped with two AC power cords that are appropriate for use in a typical 
outlet in the destination country. Each power cord connects one of the power supplies in a 
module to an independent, external power source, such as a wall receptacle or 
uninterruptible power supply (UPS). If you have a rackmount cabinet with internal power 
cabling, such as a ladder cable, you do not need these power cords.
Typically, a rackmount cabinet has two AC power distribution boxes with separate power 
cords (
. To ensure redundancy, each power cord must connect to an 
independent, external power source. Each AC power distribution box has a ladder cable 
that runs up the inside of the cabinet and connects to one of the power supplies in each 
module.
 shows the power cords and receptacles for domestic and 
international use.
Table  3-9    FC-2 14x Drive Module Power Requirements
Item
Unit of Measure
Requirement
Circuit Breaker
Slow-blow Fuse
10 A per Power Supply
AC Power
Low Range
High Range
Nominal Voltage
90 to 136 VAC
198 to 264 VAC
Frequency
50 to 60 Hz
50 to 60 Hz
Idle Current
2.93 A
1
1.27 A
2
Maximum Operating Current
3.18 A
1
1.37 A
2
Maximum Surge Current
5.85 A
1
2.36 A
2
1
Typical current: 100 V AC, 60 Hz at 0.73 power efficiency, 0.99 power factor.
2
Typical current: 240 V AC, 60 Hz at 0.73 power efficiency, 0.99 power factor.