Справочник Пользователя для LSI AP1172-E1

Скачать
Страница из 70
 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements
Command Module and Drive Module Site Preparation Guide
4-7
Environmental Requirements
The array modules are designed to operate in the environment defined in 
.
Table  4-4    Array Module Environmental Requirements
Condition
Parameter
Requirement
E2400 10x and E2400 14x 
Temperature
Operating Range
10
°
 C to 40
°
 C (50
°
 F to 104
°
 F)
Maximum Rate of Change 
10
°
 C (18
°
 F) per hour
Storage Range
-10
°
 C to 50
°
 C (14
°
 F to 122
°
 F)
Maximum Rate of Change 
15
°
 C (27
°
 F) per hour
Transit Range
-40
°
 C to 60
°
 C (-40
°
 F to 140
°
 F)
Maximum Rate of Change 
20
°
 C (36
°
 F) per hour
Relative Humidity 
No condensation
Operating Range
20% to 80%
Storage Range
10% to 90%
Transit Range
5% to 95%
Maximum Dew Point
26
°
 C (79
°
 F)
Maximum Gradient
10% per hour
Sound
Sound Power
6.0 bels
Sound Pressure
60 dBA
Altitude
(Above Sea Level)
Operating and Storage 
3000 m (9840 ft.)
Transit
12,000 m (40,000 ft.)
Altitude
(Below Sea Level)
 
Operating, Storage,
and Transit
30.5 m (100 ft.) 
1
If you plan to operate an array module at altitudes between 1000 m to 3000 m (3280 ft. to 9850 ft.) above sea level, 
lower the environmental temperature 1.7
°
 C (3.3
°
 F) for every 1000 m (3280 ft.) above sea level.
Table  4-5    Array Module Heat Dissipation
Model
Low Profile (LP)
18 GB and 36 GB Drives
Half Height (HH)
36 GB and 73 GB Drives
E2400 10x
1187 Btu/hr (0.35 kVA or 347 W)
1221 Btu/hr (0.37 kVA or 357 W)
E2400 14x
1118 Btu/hr (0.328 kVA or 327 W)
Not applicable.