Справочник Пользователя для Schneider Electric Altivar 12
90
BBV28581 05/2010
High speed configuration
The logic inputs enable selection of the desired high speed.
Desired
High speed
High speed
Setting
Parameter
State
HSP
SH2
nO
SH4
nO
HSP2
SH2
assigned
SH4
nO
HSP3
SH2
nO
SH4
assigned
HSP4
SH2
assigned
SH4
assigned
Code
Name/Description
Adjustment range
Factory setting
FUn-
Function menu
(continued)
SPL-
Speed limit menu
HSP
T
M High speed
LSP to tFr
50 or 60 Hz
according to BFr,
max TFr
according to BFr,
max TFr
Motor frequency at maximum reference, can be set between
page
.
If
tFr
is decreased below the value defined for
HSP
, then
HSP
automatically decreases to the new
value of
tFr
.
SH2
M 2 HSP assignment
nO
nO
L1H
L2H
L3H
L4H
L2H
L3H
L4H
v
No
v
L1h:
LI1 active high
v
L2h:
LI2 active high
v
L3h:
LI3 active high
v
L4h:
LI4 active high
SH4
M 4 HSP assignment
nO
nO
L1H
L2H
L3H
L4H
L2H
L3H
L4H
v
No
v
L1h:
LI1 active high
v
L2h:
LI2 active high
v
L3h:
LI3 active high
v
L4h:
LI4 active high
HSP2
T
M High speed 2
LSP to tFr
as HSP
is not set to
nO
.
HSP3
T
M High speed 3
LSP to tFr
as HSP
is not set to
nO
.
HSP4
T
M High speed 4
LSP to tFr
as HSP
are not set to
nO
.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-