10   HIGH-LEVEL POSITIONING CONTROL 
 
10.3.5 Simultaneous start   
In a "simultaneous start", the positioning data set in the "   Da.12   Start data No." and 
positioning data of other axes set in the "condition data" are simultaneously executed 
(pulses are output with the same timing).   
(The "condition data" is designated with "   Da.14   Parameter".) 
 
Section [2] shows a control example where the " block start data" and "positioning 
data" are set as shown in section [1].   
 
[1]   Setting examples 
 
(1)      Block start data setting example 
 
Axis 1 block 
start data 
 Da.11 
 
Shape 
 Da.12 
 
Start data No.
 Da.13 
 
Special start 
instruction 
 Da.14 
 
Parameter
1st point 
0: End 
3: Simultaneous start 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  It is assumed that the "axis 2 positioning data" for simultaneous starting is set in the 
"condition data" designated with "   Da.14   Parameter". 
(2)      Positioning data setting example 
 
Axis 1 positioning 
data No. 
 Da.1 
 
Operation pattern 
01: Continuous positioning control
01: Continuous positioning control
3 00: 
Positioning 
complete 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
[2]   Control examples 
The following shows the control executed when the " block start data" of the 1st 
point of axis 1 is set as shown in section [1] and started.   
<1>  Check the axis operation status of axis 2 which is regarded as the 
simultaneously started axis. 
  Axis 2 is standing by 
  Go to <2>. 
  Axis 2 is carrying out positioning. 
  An error occurs and 
simultaneous start will not be carried out. 
<2> Simultaneously start the axis 1 "positioning data No. 1" and axis 2 
positioning data set in "condition data No. 4".