Справочник Пользователя для Honeywell W7750A

Скачать
Страница из 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
33
74-2958—1
Table 8. VA Ratings For Transformer Sizing.
For contactors and similar devices, the in-rush power ratings 
should be used as the worst case values when performing 
power budget calculations. Also, the application engineer 
must consider the possible combinations of simultaneously 
energized outputs and calculate the VA ratings accordingly. 
The worst case, that uses the largest possible VA load, should 
be determined when sizing the transformer.
LINE LOSS
Excel 10 Controllers must receive a minimum supply voltage 
of 20 Vac. If long power or output wire runs are required, a 
voltage drop due to Ohms Law (I x R) line loss must be 
considered. This line loss can result in a significant increase in 
total power required and thereby affect transformer sizing. 
The following example is an I x R line-loss calculation for a 
200 ft. (61m) run from the transformer to a W7750 Controller 
drawing 37 VA using two 18 AWG (1.0 mm
2
) wires.
The formula is:
Loss =
[length of round-trip wire run (ft.)] X [resistance in 
wire (ohms per ft.)] X [current in wire (amperes)]
From specification data:
18 AWG twisted pair wire has 6.52 ohms per 1000 feet.
Loss =  [(400 ft.) X (6.52/1000 ohms per ft.)] X 
[(37 VA)/(24V)] = 4.02 volts
This means that four volts are going to be lost between the 
transformer and the controller; therefore, to assure the 
controller receives at least 20 volts, the transformer must 
output more than 24 volts. Because all transformer output 
voltage levels depend on the size of the connected load, a 
larger transformer outputs a higher voltage than a smaller one 
for a given load. Fig. 21 shows this voltage load dependence.
In the preceding I x R loss example, even though the 
controller load is only 37 VA, a standard 40 VA transformer is 
not sufficient due to the line loss. From Fig. 21, a 40 VA 
transformer is just under 100 percent loaded (for the 37 VA 
controller) and, therefore, has a secondary voltage of 22.9 
volts. (Use the lower edge of the shaded zone in Fig. 21 that 
represents the worst case conditions.) When the I x R loss of 
four volts is subtracted, only 18.9 volts reaches the controller, 
which is not enough voltage for proper operation.
In this situation, the engineer basically has three alternatives:
1.
Use a larger transformer; for example, if an 80 VA 
model is used, see Fig. 21, an output of 24.4 volts 
minus the four volt line loss supplies 20.4V to the 
controller. Although acceptable, the four-volt line-loss in 
this example is higher than recommended. See the 
following IMPORTANT.
2.
Use heavier gauge wire for the power run. 14 AWG (2.0 
mm
2
) wire has a resistance of 2.57 ohms per 1000 ft. 
which, using the preceding formula, gives a line-loss of 
only 1.58 volts (compared with 4.02 volts). This would 
allow a 40 VA transformer to be used. 14 AWG (2.0 
mm
2
) wire is the recommended wire size for 24 Vac 
wiring.
3.
Locate the transformer closer to the controller, thereby 
reducing the length of the wire run, and the line loss. 
The issue of line-loss is also important in the case of the 
output wiring connected to the Triac digital outputs. The 
same formula and method are used. The rule to 
remember is to keep all power and output wire runs as 
short as practical. When necessary, use heavier gauge 
wire, a bigger transformer, or install the transformer 
closer to the controller.
IMPORTANT
No installation should be designed where the line 
loss is greater than two volts to allow for nominal 
operation if the primary voltage drops to 102 Vac 
(120 Vac minus 15 percent).
To meet the National Electrical Manufacturers Association 
(NEMA) standards, a transformer must stay within the NEMA 
limits. The chart in Fig. 21 shows the required limits at various 
loads.
With 100 percent load, the transformer secondary must 
supply between 23 and 25 volts to meet the NEMA standard. 
When a purchased transformer meets the NEMA standard 
DC20-1986, the transformer voltage-regulating ability can be 
considered reliable. Compliance with the NEMA standard is 
voluntary.
The following Honeywell transformers meet this NEMA 
standard:
Transformer Type
VA Rating
AT20A
20
AT40A
40
AT72D
40
AT87A
50
AK3310 Assembly
100
Device
Description
VA
W7750A
Excel 10 W7750 Controller
6.0
W7750B,C
Excel 10 W7750 Controllers
12.0
ML6161A/B
Damper Actuator, 35 lb-in.
2.2
R8242A
Contactor
21.0
M6410A
Valve Actuator
0.7
MMC325
Pneumatic Transducer
5.0
ML684
Versadrive Valve Actuator
12.0
ML6464
Damper Actuator, 66 lb-in.
3.0
ML6474
Damper Actuator, 132 lb-in.
3.0
ML6185
Damper Actuator SR 50 lb-in.
12.0
ML7984B
PWM Valve Actuator
6.0