EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
35
74-2958—1
Fig. 24. Transformer power wiring details for one Excel 10 
used in UL 1995 equipment (U.S. only).
IMPORTANT
Notes on power wiring:
All field wiring must conform to local codes and ordi-
nances or as specified on installation wiring dia-
grams.
To maintain NEC Class 2 and UL ratings, the instal-
lation must use transformers of 100 VA or less 
capacity.
For multiple controllers operating from a single trans-
former, the same side of the transformer secondary 
must be connected to the same input terminal in 
each controller (21 on the W7750A and 24 on the 
W7750B,C) and the ground terminals must be con-
nected to a verified earth ground for each controller 
in the group. See Fig. 23. (Controller configurations 
are not necessarily limited to three devices per trans-
former.)
For the W7750B,C Controller (which has Triac out-
puts), all output devices must be powered from the 
same transformer as the one powering the Excel 10 
W7750 Controller.
Use the heaviest gauge wire available, up to 14 
AWG (2.0 mm
2
) with a minimum of 18 AWG (1.0 
mm
2
) for all power and earth ground connections.
To minimize EMI noise, do not run Triac output wires 
in the same conduit as the input wires or the L
ON
-
W
ORKS
 Bus communications wiring.
Unswitched 24 Vac power wiring can be run in the 
same conduit as the L
ON
W
ORKS
 Bus cable.
Make earth ground connections with the shortest 
possible wire run using 14 AWG (2.0 mm
2
) wire. A 
good earth ground is essential for W7750 operation. 
Ideally, connect the earth ground to the ground bus 
at a motor control center or circuit breaker panel. 
However, if the nearest ideal earth ground is inac-
cessible, consider an alternate source for earth 
ground. Metal water pipe is generally a good ground, 
but do not use sprinkler pipe if prohibited by local 
codes. Attention must be given when duct work, con-
duit, or rebar are to be considered as ground 
sources. It is the responsibility of the installer to 
assure that these structures are tied back to a known 
earth ground.
Step 4. Prepare Wiring Diagrams
General Considerations
The purpose of this step is to assist the application engineer in 
developing job drawings to meet job specifications. Wiring 
details are included for the W7750A,B,C Controllers and the 
T7770 and T7560A,B Wall Modules. The drawings detail I/O, 
power, and L
ON
W
ORKS
 Bus communication wiring 
connections.
NOTE:
For field wiring, when two or more wires, other than 
14 AWG (2.0 mm
2
) are to be attached to the same 
connector block terminal, be sure to twist them 
together. Deviation from this rule can result in 
improper electrical contact. See Fig. 25.
The connector block terminals on the W7750 Controllers and 
on the T7770 Wall Modules accept 14 through 22 AWG (2.0 to 
0.34 mm
2
) wire. The connector block terminals on the 
T7560A,B Wall Modules accept 18 through 22 AWG (1.0 to 
0.34 mm
2
) wire. Table 9 lists wiring types, sizes, and length 
restrictions for Excel 10 products.
M10088A
24 VAC
LINE VOLTAGE
GREATER
THAN 150 VAC
TRANSFORMER
W7750
EARTH
GROUND
EARTH
GROUND
IF THE W7750 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE 
PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND 24 VAC COM 
SIDE OF TRANSFORMER SECONDARY.
1
1
1