6 - 62 
MELSEC-A
6   SEQUENCE PROGRAM USED FOR POSITIONING CONTROL 
 
(3)   Control data requiring setting 
Set the following data to execute restart. 
 
Setting item 
Setting 
value 
Setting details 
Remote input/output 
Axis 1 
Axis 2 
Restart command 
Set "1: restarts ". 
RY(n+2)5  RY(n+4)5
 
                 *  Refer to section "3.4 Specifications of input/output signals for master module" for details on the setting details. 
 
 
(4)   Starting conditions 
The following conditions must be satisfied when restarting. (Assemble the 
required conditions into the sequence program as an interlock.) 
 
(1) Operation state 
 
"Axis operation status (RWrn+7, RWrn+15)" is "1: Stopped" 
 
(2) Signal state 
 
Signal name 
Signal state 
Device 
Axis 1 
Axis 2 
Interface 
signal 
Remote station READY 
signal 
ON Positioning operation possible 
RX(n+7)B 
D75P2 READY signal 
OFF D75P2 preparation completed 
RXn0 
Axis stop signal 
OFF Axis stop signal is OFF 
RY(n+1)3  RY(n+1)4
Start complete signal 
OFF Start complete signal is OFF 
RXn1 
RXn2 
BUSY signal 
OFF BUSY signal is OFF 
RXn4 
RXn5 
Error detection signal 
OFF There is no error 
RXnA 
RXnB 
M code ON signal 
OFF M code ON signal is OFF 
RXnD 
RXnE 
External 
signal 
Drive unit READY signal ON Drive unit preparation completed  RX(n+1)2  RX(n+4)2
Stop signal 
OFF Stop signal is OFF 
RX(n+1)6  RX(n+4)6
Upper limit (FLS) 
ON Within limit range 
RX(n+1)7  RX(n+4)7
Lower limit (RLS) 
ON Within limit range 
RX(n+1)8  RX(n+4)8