9 - 23 
MELSEC-A
9   MAIN POSITIONING CONTROL 
 
9.2.2 1-axis linear control 
In "1-axis linear control" ("
Da.2  Control method" = ABS linear 1, INC linear 1), one 
motor is used to carry out position control in a set axis direction.  
 
(1)   1-axis linear control (ABS linear 1) 
 
 Operation chart 
 
In absolute system 1-axis linear control, addresses established by a machine zero 
point return are used. Positioning is carried out from the current stop position (start 
point address) to the address (end point address) set in " Da.5  Positioning 
address/movement amount". 
 
0
1000
8000
Positioning control (movement amount 7000)
Start point address
(current stop position)
End point address
(positioning address
Example
When the start point address (current stop position) is 1000, and the end point address (positioning address) is 8000,
positioning is carried out in the positive direction for a movement amount of 7000 (8000-1000)
 
 
 Positioning data setting example 
 
The following table shows setting examples when "1-axis linear control (ABS linear 
1)" is set in positioning data No. 1 of axis 1.  
 
Setting item 
Setting example
Setting details 
Axis 1   Positio
ning data N
o. 1
 
Da.1
 Operation pattern 
Positioning 
complete 
Set "Positioning complete" assuming the next positioning data will not 
be executed. 
Da.2
 Control method 
ABS linear 1  Set absolute system 1-axis linear control. 
Da.3
 
Acceleration time 
No. 
Designate the value set in "
Pr.26  Acceleration time 1" as the 
acceleration time at start. 
Da.4
 
Deceleration time 
No. 
Designate the value set in " Pr.9  Deceleration time 0" as the 
deceleration time at deceleration. 
Da.5
 
Positioning address/ 
movement amount 
8000.0
Set the positioning address. (Assuming "mm" is set in " Pr.1  Unit 
setting".) 
Da.6
 Arc address 
– 
Setting not required (setting value will be ignored). 
Da.7
 Command speed 
6000.00mm/min Set the speed during movement to the positioning address. 
Da.8
 Dwell time 
500ms 
Set the time the machine dwells after the positioning stop (pulse output 
stop) to the output of the positioning complete signal. 
Da.9
 M code 
10 
Set this when other auxiliary operation commands are issued in 
combination with the No. 1 positioning data. 
 
   * Refer to section "5.3 List of positioning data" for information on the setting details.