Справочник Пользователя для Mitsubishi Electronics AJ65BT-D75P2-S3

Скачать
Страница из 666
 
 
 
10 - 11 
MELSEC-A
10   ADVANCED POSITIONING CONTROL 
 
10.3.4 Wait start 
In a "wait start", the "condition data" conditional judgment designated in "
Da.13  
Parameter" is carried out for the positioning data set in " Da.11   Start data No.". If the 
conditions have been established, the "start block data" is executed. If the conditions 
have not been established, the control stops (waits) until the conditions are 
established.  
 
Section (2) shows a control example where the "start block data" and "positioning data" 
are set as shown in section (1).   
 
(1)   Setting examples 
 
(a)      Start block data setting example 
 
Axis 1 start 
block data 
Da.10  Shape
Da.11  Start 
data No. 
Da.12  Special 
start command 
Da.13  
Parameter 
1st point 
1: Continue 
2: Wait start 
2nd point 
1: Continue 
10 
0: Normal start 
– 
3rd point 
0: End 
50 
0: Normal start 
– 
 
 
 
 
 
 
 
 
 
 
 
* The "condition data Nos." have been set in " Da.13  Parameter". 
 
(b)      Positioning data setting example 
 
Axis 1 position-
ing data No. 
Da.1  Operation pattern 
01: Continuous positioning control
01: Continuous positioning control
3 00: 
Positioning 
complete 
 
 
10 
11: Continuous path control 
11 
11: Continuous path control 
12 00: 
Positioning 
complete 
 
 
50 00: 
Positioning 
complete 
 
 
 
(2)   Control examples 
The following shows the control executed when the "start block data" of the 1st 
point of axis 1 is set as shown in section (1) and started.   
 
<1>  The conditional judgment set in "condition data No. 3" is carried out before 
execution of the axis 1 "positioning data No. 1". 
  Conditions established 
  Execute positioning data No. 1, 2, and 3 
 
Go to <2>. 
  Conditions not established 
  Control stops (waits) until conditions are 
established 
  Go to <1>. 
 
<2> Execute the axis 1 "positioning data No. 10, 11, 12, and 50" and stop the 
control.