11   MANUAL CONTROL 
 
11.3.2 Manual pulse generator operation execution procedure 
The manual pulse generator operation is carried out by the following procedure.  
 
* Write the sequence program created in 
   STEP 1 and STEP 2 to the PLC CPU. 
* Set the control data and create a sequence
   program to enable/disable the manual pulse
   generator operation. (Set the control data
   in the D75P2 buffer memory using the TO
   command(dedicated command).) 
* Directly set (write) the parameters in the D75P2 
  using the AD75 software package. 
STEP 1
 
 
 
Manual pulse
generator operation
start
 
 
 
 
End of control
 
 
 
STEP 2
 
 
 
STEP 3
 
 
STEP 4
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
STEP 5
 
 
 
 
 
 
 
 
 
Issue a command to enable the manual pulse generator
operation, and input the signals from the manual pulse
generator. 
 
End the input from the manual pulse generator, 
and issue a command to disable the manual pulse 
 
Manual pulse
generator operation
stop
 
 
STEP 6
Monitor the manual pulse generator operation.
 
Preparation
Refer to Chapter 5
and section 11.3.3.
Refer to section
11.3.4.
Set the parameters 
Write the sequence program to the PLC CPU.
* Monitor using the AD75 software package.
Monitoring of the
manual pulse
generator operation
Set "  Cd. 23  Manual pulse generator 1 pulse input
magnification." (control data setting)
to
)
Pr.1
)
Pr.24
Create a sequence program in which the enable/disable is
 
 
(
"
Manual pulse generator enable flag (RY(n+2)9, RY(n+4)9)
"
 setting.)
set for the manual pulse generator operation. 
* Stop operating the manual pulse generator, and
  write "0" in "Manual pulse generator enable flag
  (RY(n+2)9, RY(n+4)9)"
 
 
 * Write "1" in "Manual pulse generator enable 
    flag (RY(n+2)9, RY(n+4)9)", and operate
    the manual pulse generator. 
 
 
 
 
 
 
REMARK 
 Mechanical elements such as limit switches are considered as already installed.  
 Parameter settings work in common for all control using the D75P2.