Справочник Пользователя для Mitsubishi Electronics AJ65BT-D75P2-S3

Скачать
Страница из 666
 
 
 
11 - 21 
MELSEC-A
11   MANUAL CONTROL 
 
11.3.4 Starting the manual pulse generator operation  
A sequence program must be created to execute a manual pulse generator operation. 
Consider the "required control data setting", "start conditions", "start time chart", and 
"device settings" when creating the program.  
The following shows an example when a manual pulse generator operation is started 
for axis 1. 
 
 Required control data setting 
 
The control data shown below must be set to execute a manual pulse generator 
operation. The setting is carried out with the sequence program.  
 
Setting item 
Setting 
value 
Setting details 
Remote input/output, 
buffer memory address
Axis 1 
Axis 2 
Manual pulse generator 
enable flag 
ON 
Set "ON: Enable manual pulse generator 
operation". (Set "OFF: Disable manual pulse 
generator operation" when finished with the 
manual pulse generator operation.) 
RY(n+2)9 RY(n+4)9
Cd.23  
Manual pulse 
generator 1 pulse 
input 
magnification 
Set the manual pulse generator 1 pulse input 
magnification. 
1168 
1169 
1218 
1219 
 
                 * Refer to section "3.4 Specifications of input/output signals for master module", "5.7 List of control data" for 
details on the setting details. 
 
 
 Start conditions  
 
The following conditions must be fulfilled when starting. The required conditions 
must also be assembled in the sequence program, and the sequence program 
must be configured so the operation will not start if the conditions are not fulfilled.  
 
Signal name 
Signal state 
Device 
Axis 1 
Axis 2 
Interface 
signal 
Remote station READY 
signal 
ON Positioning operation possible 
RX(n+7)B 
D75P2 READY signal 
OFF D75P2 preparation completed 
RXn0 
Axis stop signal 
OFF Axis stop signal is OFF 
RY(n+1)3  RY(n+1)4
Start complete signal 
OFF Start complete signal is OFF 
RXn1 
RXn2 
BUSY signal 
OFF BUSY signal is OFF 
RXn4 
RXn5 
Error detection signal 
OFF There is no error 
RXnA 
RXnB 
M code ON signal 
OFF M code ON signal is OFF 
RXnD 
RXnE 
External 
signal 
Drive unit READY signal ON Drive unit preparation completed  RX(n+1)2  RX(n+4)2
Stop signal 
OFF Stop signal is OFF 
RX(n+1)6  RX(n+4)6
Upper limit (FLS) 
ON Within limit range 
RX(n+1)7  RX(n+4)7
Lower limit (RLS) 
ON Within limit range 
RX(n+1)8  RX(n+4)8