MELSEC-A
12   CONTROL AUXILIARY FUNCTIONS 
 
(4)   Setting the torque limit function 
 
(a)  To use the "torque limit function", set the "torque limit value" in the 
parameters shown in the following table, and write them to the D75P2.  
The set details are validated at the rising edge (OFF   ON) of the remote 
station READY signal [RX(n+7)B]. 
 
Setting item 
Setting 
value 
Setting details 
Factory-set 
initial value 
Pr.18  
Torque limit 
setting value 
 
Set the torque limit value as a percentage. 
300 
Pr.56  
Zero point return 
torque limit value 
 
Set the torque limit value to be used after starting the 
deceleration to the " Pr.49  Creep speed" with %. 
300 
 
                  * Refer to section "5.2 List of parameters" for setting details. 
 
(b)  The "torque limit value" set in the D75P2 is set in the "
Md.45  Torque limit 
stored value". The " Md.45  Torque limit stored value" in the sequence 
program is transferred to the "D/A converter module", and the torque is 
limited.  
 
PLC CPU
Buffer memory
Drive unit 
Writing by a
TO command
Stored torque
 limit value 
826
D/A convertor module
Reading by a 
FROM command
(dedicated 
 command)
D75P2
Torque limiting
Positioning control 
 
Fig. 12.14 Limiting the torque to the drive unit 
 
The following table shows the " Md.45  Torque limit stored value" of the 
buffer memory address.  
 
Monitor item 
Monitor 
value 
Storage details 
Buffer memory address
Axis 1 
Axis 2 
Md.45  
Torque limit 
stored value 
 
The "torque limit value" valid at that time is 
stored. ( Pr.18 ,  Pr.56 , or  Cd.30 ) 
826 926 
 
                  * Refer to section "5.6 List of monitor data" for information on the setting details. 
 
REMARK 
 Parameters are set for each axis.