13 - 10 
MELSEC-A
13   COMMON FUNCTIONS 
 
13.5 Clock data function 
"The clock data function" utilizes the PLC CPU clock data in the D75P2.   
This clock data is used to monitor 
Md.7  to  Md.12 , Md.13  to  Md.18 ,  Md.19  to 
Md.23 , Md.24  to  Md.28   history data. The clock data is controlled in 0.1 second 
units in the D75P2 to simplify the measurement of cycle time, etc.     
 
The details shown below explain about the "clock data setting function".   
   (1) Precautions during control 
      (2) Setting the clock data 
 
 
(1)   Precautions during control 
 
(a)  Set the clock data every time the D75P2 is started. If the clock data is not 
set, counting will begin as "00 hours 00 minute 00 seconds" when the 
D75P2 starts.   
(b)  The D75P2 clock data count value is less accurate that the PLC CPU clock 
data. Therefore, synchronize it with the PLC CPU clock data about once a 
day.  
(c)  Data indicating the "date" in the PLC CPU clock data will be ignored.   
 
(2)   Setting the clock data 
The following shows the example setting data for reading the PLC CPU clock 
data and setting it in the D75P2. 
 
(a)   Set the following data.  
 
Setting item 
Setting 
value 
Setting details 
Buffer memory address
Axis 1 
Axis 2 
Cd.1  
Clock data setting 
(hour) 
 
Set the PLC CPU clock data (hours). 
1100 
Cd.2  
Clock data setting 
(minute, second) 
 
Set the PLC CPU clock data (minutes, 
seconds). 
1101 
Cd.3   Clock data writing 
Set "1" (clock data write request). 
1102 
 
                 * Refer to section "5.7 List of control data" for details on the setting details.