4.3  CHANGING THE ENGINE OIL
4.3.1  OIL CHANGE INTERVALS
See the "Service Schedule" section.
4.3.2  ENGINE OIL RECOMMENDATIONS
All oil should meet minimum American Petroleum 
Institute (API) Service Class SJ, SL or better. Use 
no special additives. Select the oil's viscosity grade 
according to the expected operating temperature.
  Any attempt to crank or start the engine before 
it has been properly serviced with the recom-
mended oil may result in an engine failure.
1 0 W - 3 0
1 0 W - 3 0
S A E   3 0
S A E   3 0
S y n t h e t i c   5 W - 3 0
S y n t h e t i c   5 W - 3 0
4.3.3  OIL & OIL FILTER CHANGE PROCEDURE
To change the oil, proceed as follows:
1.  Start the engine by moving the AUTO/OFF/
MANUAL switch to MANUAL and run until it 
is thoroughly warmed up. Then shut OFF the 
engine by moving the switch to the OFF position.
2.  Immediately after the engine shuts OFF, pull the 
oil drain hose (Figure 4.5) free of its retaining 
clip. Remove the cap from the hose and drain the 
oil into a suitable container.
3.  After the oil has drained, replace the cap onto the 
end of the oil drain hose. Retain the hose in the 
clip.
Change the engine oil filter as follows:
1.  With the oil drained, remove the old oil filter by 
turning it counterclockwise.
2.  Apply a light coating of clean engine oil to the gas-
ket of the new filter. See the Specifications section 
for recommended filter.
3.  Screw the new filter on by hand until its gasket 
lightly contacts the oil filter adapter. Then, tighten 
the filter an additional 3/4 to one turn (Figure 
4.4).
‹
‹
‹
Figure 4.5 – Oil Drain Hose and Filter
Oil Filter
Oil
Drain
Hose
Low Oil Switch
High Temp Switch
     Loose
4.  Refill with the proper recommended oil (see the 
Engine Oil Recommendations section). See the 
Specifications section for oil capacities.
5.  Start the engine, run for one (1) minute, and 
check for leaks.
6.  Shutdown and recheck oil level, add as needed. 
DO NOT OVER FILL.
7.  Reset the AUTO/OFF/MANUAL switch to the 
AUTO position.
4.4  
CHANGING THE ENGINE 
AIR CLEANER
4.4.1  7, 13, AND 16KW GENERATORS
See Figures 1.1 and 1.2, for the location of the air 
cleaner. Use the following procedures (Figure 4.6, 
7kW; Figure 4.8, 13/16kW):
1.  Lift the roof and remove the door.
2.  Turn the two screws counterclockwise to loosen.
3.  Remove the cover and air filter.
4.  Wipe away dust or debris from inside of the air 
box and around edges.
5.  Install the new air cleaner into the air box.
6.  Install the cover. Turn the two cover screws clock-
wise to tighten.
See the Service Schedule section for air cleaner main-
tenance. See the Specifications section for air filter 
replacement part number.
‹
Section 4 — Maintenance
Air-cooled Generators